Plan Review Notes For Permit 10040320
Permit Number 10040320
Review Stop P
Sequence Number 1
Notes
Date Text
2010-04-19 13:40:33FBC 2007
 REVIEW: DENIED
  
 SHEET P6.1
 IF THIS IS AN INDIVIDUALLY VENTED SYSTEM THEN THESE
 VENTS THAT ARE SHOWN ON THE MAIN NEED TO BE ON THE
 BRANCH OFF OF THE MAIN.
 1. SAN RISER "E" - SH-1 IN BATHROOM 115 REQUIRES A VENT
 ON THE BRANCH.
 2. SAN RISER "F" - WC-1 IN BATHROOM 207 REQUIRES A VENT
 ON THE BRANCH.
 SH-1 IN BATHROOM 217 REQUIRES A VENT ON THE BRANCH.
 WC-1 & SH-1 IN BATHROOM 117 REQUIRE A VENT ON THE
 BRANCHS.
 3. SAN RISER "I" WC-1 & SH-1WOULD REQUIRE VENTS ON THE
 BRANCHES AS KITCHEN SINKS ARE NOT PERMITTED ON WET
 VENTS FBC 2007 PLUMBING 909.1
 4. SAN RISER "A" WC-1 & SH-1 IN BATHROOM 119 REQUIRE A
 VENT ON THE BRANCHS.
  
 REVIEW BY LARRY WAGNER