Plan Review Notes For Permit 10040320 |
Permit Number |
10040320 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-04-19 13:40:33 | FBC 2007 | | REVIEW: DENIED | | | | SHEET P6.1 | | IF THIS IS AN INDIVIDUALLY VENTED SYSTEM THEN THESE | | VENTS THAT ARE SHOWN ON THE MAIN NEED TO BE ON THE | | BRANCH OFF OF THE MAIN. | | 1. SAN RISER "E" - SH-1 IN BATHROOM 115 REQUIRES A VENT | | ON THE BRANCH. | | 2. SAN RISER "F" - WC-1 IN BATHROOM 207 REQUIRES A VENT | | ON THE BRANCH. | | SH-1 IN BATHROOM 217 REQUIRES A VENT ON THE BRANCH. | | WC-1 & SH-1 IN BATHROOM 117 REQUIRE A VENT ON THE | | BRANCHS. | | 3. SAN RISER "I" WC-1 & SH-1WOULD REQUIRE VENTS ON THE | | BRANCHES AS KITCHEN SINKS ARE NOT PERMITTED ON WET | | VENTS FBC 2007 PLUMBING 909.1 | | 4. SAN RISER "A" WC-1 & SH-1 IN BATHROOM 119 REQUIRE A | | VENT ON THE BRANCHS. | | | | REVIEW BY LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | (561) 805-6692 | | FAX (561) 653-2692 | | E-MAIL [email protected] | | |
|