2010-04-28 13:59:33 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE POWER PLAN NOTES (ALL UNITS) SHOULD INCLUDE
 NOTING " 406.11 TAMPER-RESISTANT RECEPTACLES IN
 DWELLING UNITS.IN ALL AREAS SPECIFIED IN 210.52, ALL
 125-VOLT, 15- AND 20-AMPERE RECEPTACLES SHALL BE LISTED
 TAMPER-RESISTANT RECEPTACLES".TO AVOID CONFUSION IN THE
 FIELD.
  
 2} ALL RISER DIAGRAMS SHALL INDICATE COMPLIANCE WITH
 250.94: REVISED TO PROVIDE THE SPECIFIC MEANS FOR
 INTERSYSTEM BONDING CONNECTIONS AND TO PROHIBIT BONDING
 MEANS ATTACHED TO AN ENCLOSURE FROM INTERFERING WITH
 OPENING OR REMOVAL OF THE ENCLOSURE COVER.
  
 3} 210.52(B)(3) KITCHEN RECEPTACLE REQUIREMENTS.
 RECEPTACLES INSTALLED IN A KITCHEN TO SERVE COUNTERTOP
 SURFACES SHALL BE SUPPLIED BY NOT FEWER THAN TWO
 SMALL-APPLIANCE BRANCH CIRCUITS, EITHER OR BOTH OF
 WHICH SHALL ALSO BE PERMITTED TO SUPPLY RECEPTACLE
 OUTLETS IN THE SAME KITCHEN AND IN OTHER ROOMS
 SPECIFIED IN 210.52(B)(1). ADDITIONAL SMALL-APPLIANCE
 BRANCH CIRCUITS SHALL BE PERMITTED TO SUPPLY RECEPTACLE
 OUTLETS IN THE KITCHEN AND OTHER ROOMS SPECIFIED IN
 210.52(B)(1).***ALL UNITSONLY HAVE ONE CIRCUIT IN THE
 KITCHEN.
  
 4} 210.52 (C) COUNTERTOPS. IN KITCHENS, PANTRIES,
 BREAKFAST ROOMS, DINING ROOMS, AND SIMILAR AREAS OF
 DWELLING UNITS, RECEPTACLE OUTLETS FOR COUNTERTOP
 SPACES SHALL BE INSTALLED IN ACCORDANCE WITH
 210.52(C)(1) THROUGH (C)(5).210.52 (C)(1) WALL
 COUNTERTOP SPACES. A RECEPTACLE OUTLET SHALL BE
 INSTALLED AT EACH WALL COUNTERTOP SPACE THAT IS 300 MM
 (12 IN.) OR WIDER. RECEPTACLE OUTLETS SHALL BE
 INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE
 THAN 600 MM (24 IN.) MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE.*** SEE UNITS A,E & F.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  