2010-08-02 13:49:27 | PLUMBING REVIEW #3 |
| DENIED: |
| |
| FBC PLUMBING 2007 1003.3.1 |
| |
| WITH THE INCLUSION OF THE RANGE THE BREAKROOM APPEARS |
| TO BE A COMMERCIAL KITCHEN, PLEASE ADDRESS. |
| A COMMERCIAL KITCHEN WILL REQUIRE: |
| |
| 1. THREE COMPARTMENT SINK WITH INDIRECT WASTE 802.1.1 |
| |
| 2. GREASE TRAP OR INTERCEPTOR 1003.3.1: |
| 1003.3.1 GREASE INTERCEPTORS AND AUTOMATIC GREASE |
| REMOVAL DEVICES REQUIRED. A GREASE INTERCEPTOR OR |
| AUTOMATIC GREASE REMOVAL DEVICE SHALL BE REQUIRED TO |
| RECEIVE THE DRAINAGE FROM FIXTURES AND EQUIPMENT WITH |
| GREASE-LADEN WASTE LOCATED IN FOOD PREPARATION AREAS, |
| SUCH AS IN RESTAURANTS, HOTEL KITCHENS, HOSPITALS, |
| SCHOOL KITCHENS, BARS, FACTORY CAFETERIAS AND CLUBS. |
| FIXTURES AND EQUIPMENT SHALL INCLUDE POT SINKS, |
| PRERINSE SINKS; SOUP KETTLES OR SIMILAR DEVICES; WOK |
| STATIONS; FLOOR DRAINS OR SINKS INTO WHICH KETTLES ARE |
| DRAINED; AUTOMATIC HOOD WASH UNITS AND DISHWASHERS |
| WITHOUT PRERINSE SINKS. GREASE INTERCEPTORS AND |
| AUTOMATIC GREASE REMOVAL DEVICES SHALL RECEIVE WASTE |
| ONLY FROM FIXTURES AND EQUIPMENT THAT ALLOW FATS, OILS |
| OR GREASE TO BE DISCHARGED. |
| |
| |
| 3. DISHWASHER REQUIRES AN INDIRECT WASTE ROUTED TO THE |
| GREASE TRAP. EXCEPTION : DISHWASHER WITH PRE-RINSE |
| SINK. 802.1.7 |
| |
| 4. THE FOOD WASTE DISPOSER WOULD BE REQUIRED TO BE |
| ROUTED TO THE SANITARY, OR A SOLIDS INTERCEPTOR WOULD |
| BE REQUIRED BEFORE CONNECTING TO THE GREASE |
| INTERCEPTOR OR GREASE TRAP. |
| |
| NOTE - GREASE INTERCEPTORS SHALL BE SIZED PER TABLE |
| 1003.3.4.1 |
| |
| REVIEW BY LARRY WAGNER |
| CHIEF PLUMBING INSPECTOR |
| (561) 805-6692 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |
| |