Plan Review Notes For Permit 10040281 |
Permit Number |
10040281 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2010-07-29 09:47:22 | PLAN DENIED | | 1) COMMENT # 2 FROM LAST REVIEW WAS NOT ANSWER , PLEASE | | PROVIDE FRESH AIR CALCULATIONS ON THE PLANS. | | 2) PLEASE REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEM | | AND 606.3 INSTALLATION 2007 FBC (M) | | 3) PLEASE PROVIDE WHAT APPLIANCES ARE IN THE KITCHEN ON | | THE PLANS. | | 4) PLEASE PROVIDE MODEL NUMBER OF THE EQUIPMENT ON THE | | EQUIPMENT SCHEDULE TO COMPLY WITH 14.4 SEER. | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|