Plan Review Notes For Permit 10040281 |
Permit Number |
10040281 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2010-08-16 08:37:55 | 1) RISER DIAGRAM SHOWS NO WIRE SIZES. | | | | 2) NEED TO SHOW SERVICE GROUNDING FOR BOTH MAINS AND | | METER | | | | 3) CIRCUIT NUMBER 6 SHOWS OUTLETS WITHIN 6' OF SINK | | THAT ARE NOT GFCI PROTECTED. | | | | 4) NEED CUT SHEETS ON THE FIXTURES TO BE ABLE TO CHECK | | WATTAGES OF THE FIXTURES | | | | 5) CIRCUITS 14,16 SHOWN AS SINGLE POLES. | | | | 6) FOR THE RECEPTACLE LOAD YOU USED 1 VA PER SQ FT THAT | | IS ONLY USED WHEN THE ACTUAL NUMBER OF OUTLETS IS | | UNKNOWN. | | | | 7) LIGHTING IS A CONTINUOUS LOAD AND SHALL BE RATED AT | | 125% | | | | 8) PLEASE CHECK YOUR NOTES ON PAGE E-001 PLAN NOTES FOR | | ALL THE MISSING EQUIPMENT NOT INCLUDED IN THE LOAD | | CALCULATION. | | 27-2, 27-4, 27-5, 27-6, 27-8. | | | | | | | | | | | | | | |
|