Date Text
2010-08-16 08:37:551) RISER DIAGRAM SHOWS NO WIRE SIZES.
  
 2) NEED TO SHOW SERVICE GROUNDING FOR BOTH MAINS AND
 METER
  
 3) CIRCUIT NUMBER 6 SHOWS OUTLETS WITHIN 6' OF SINK
 THAT ARE NOT GFCI PROTECTED.
  
 4) NEED CUT SHEETS ON THE FIXTURES TO BE ABLE TO CHECK
 WATTAGES OF THE FIXTURES
  
 5) CIRCUITS 14,16 SHOWN AS SINGLE POLES.
  
 6) FOR THE RECEPTACLE LOAD YOU USED 1 VA PER SQ FT THAT
 IS ONLY USED WHEN THE ACTUAL NUMBER OF OUTLETS IS
 UNKNOWN.
  
 7) LIGHTING IS A CONTINUOUS LOAD AND SHALL BE RATED AT
 125%
  
 8) PLEASE CHECK YOUR NOTES ON PAGE E-001 PLAN NOTES FOR
 ALL THE MISSING EQUIPMENT NOT INCLUDED IN THE LOAD
 CALCULATION.
 27-2, 27-4, 27-5, 27-6, 27-8.
  
  
  
  
  
  
  