Plan Review Notes
Plan Review Notes For Permit 10040281
Permit Number 10040281
Review Stop P
Sequence Number 2
Notes
Date Text
2010-06-09 14:02:04PLUMBING REVIEW #2
 DENIED
  
 FBC PLUMBING 2007 1003.3.1
 THE KITCHEN IN A COMMERCIAL BUILDING WILL REQUIRE:
 1. THREE COMPARTMENT SINK WITH INDIRECT WASTE 802.1.1
 2. GREASE TRAP OR INTERCEPTOR 1003.3.1
 3. DISHWASHER REQUIRES AN INDIRECT WASTE ROUTED TO THE
 GREASE TRAP. EXCEPTION : DISHWASHER WITH PRE-RINSE
 SINK. 802.1.7
 4. THE FOOD WASTE DISPOSER WOULD BE REQUIRED TO BE
 ROUTED TO THE SANITARY, OR A SOLIDS INTERCEPTOR WOULD
 BE REQUIRED BEFORE CONNECTING TO THE GREASE
 INTERCEPTOR.
  
 NOTE - GREASE INTERCEPTORS SHALL BE SIZED PER TABLE
 1003.3.4.1