Plan Review Notes For Permit 10040281 |
Permit Number |
10040281 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2010-06-09 14:02:04 | PLUMBING REVIEW #2 | | DENIED | | | | FBC PLUMBING 2007 1003.3.1 | | THE KITCHEN IN A COMMERCIAL BUILDING WILL REQUIRE: | | 1. THREE COMPARTMENT SINK WITH INDIRECT WASTE 802.1.1 | | 2. GREASE TRAP OR INTERCEPTOR 1003.3.1 | | 3. DISHWASHER REQUIRES AN INDIRECT WASTE ROUTED TO THE | | GREASE TRAP. EXCEPTION : DISHWASHER WITH PRE-RINSE | | SINK. 802.1.7 | | 4. THE FOOD WASTE DISPOSER WOULD BE REQUIRED TO BE | | ROUTED TO THE SANITARY, OR A SOLIDS INTERCEPTOR WOULD | | BE REQUIRED BEFORE CONNECTING TO THE GREASE | | INTERCEPTOR. | | | | NOTE - GREASE INTERCEPTORS SHALL BE SIZED PER TABLE | | 1003.3.4.1 |
|