Plan Review Notes
Plan Review Notes For Permit 10040272
Permit Number 10040272
Review Stop B
Sequence Number 1
Notes
Date Text
2010-04-13 11:23:17RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- ACCORDING TO SEC. R301.2.1.4.3 OF 2009 REVISIONS TO
 THE 2007 FLORIDA RESIDENTIAL CODE, THIS BUILDING IS
 LOCATED ON EXPOSURE "C" NOT "B". ENGINEER NEEDS TO
 CHANGE THE BUILDING EXPOSURE, DESIGN PRESSURES AND RAS
 117 CALCULATIONS ACCORDINGLY.
  
 2- SELECTED ASSEMBLY (PAGES 7 & 8 OF NOA 08-0227.09) IS
 LIMITED BY GENERAL LIMITATION #9. ENGINEER CAN'T
 PROVIDE NAIL ENHANCING. SEE GENERAL LIMITATION #9 ON
 LAST PAGE OF NOA SUBMITTED. NEED TO SELECT ANOTHER
 APPROVED ASSEMBLY.
  
 3- ENGINEER TO COORDINATE NAIL ENHANCING CALCULATIONS
 FOR CARPORT TO MATCH SELECTED ASSEMBLY. CARPORT DOESN'T
 HAVE AN INSULATED ASSEMBLY. COORDINATE WITH ROOFING
 CONTRACTOR.
  
 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712