Plan Review Notes For Permit 10040272 |
Permit Number |
10040272 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-04-13 11:23:17 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | 1- ACCORDING TO SEC. R301.2.1.4.3 OF 2009 REVISIONS TO | | THE 2007 FLORIDA RESIDENTIAL CODE, THIS BUILDING IS | | LOCATED ON EXPOSURE "C" NOT "B". ENGINEER NEEDS TO | | CHANGE THE BUILDING EXPOSURE, DESIGN PRESSURES AND RAS | | 117 CALCULATIONS ACCORDINGLY. | | | | 2- SELECTED ASSEMBLY (PAGES 7 & 8 OF NOA 08-0227.09) IS | | LIMITED BY GENERAL LIMITATION #9. ENGINEER CAN'T | | PROVIDE NAIL ENHANCING. SEE GENERAL LIMITATION #9 ON | | LAST PAGE OF NOA SUBMITTED. NEED TO SELECT ANOTHER | | APPROVED ASSEMBLY. | | | | 3- ENGINEER TO COORDINATE NAIL ENHANCING CALCULATIONS | | FOR CARPORT TO MATCH SELECTED ASSEMBLY. CARPORT DOESN'T | | HAVE AN INSULATED ASSEMBLY. COORDINATE WITH ROOFING | | CONTRACTOR. | | | | 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 | | FLORIDA STATUTE. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|