Plan Review Notes For Permit 10040264 |
Permit Number |
10040264 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2010-04-22 13:51:16 | REVIEW ACTION: DENIED | | | | 1. FBC 2007 106.3.5 PLUMBING SANITARY AND WATER PIPE | | ISOMETRICS REQUIRED. | | | | 2. FBC 2007 PLUMBING 403.2 SEPARATE FACILITIES. | | WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE | | FACILITIES SHALL BE PROVIDED FOR EACH SEX. | | EXCEPTIONS: | | 1. SEPARATE FACILITIES SHALL NOT BE REQUIRED FOR | | PRIVATE FACILITIES. | | 2. SEPARATE EMPLOYEE FACILITIES SHALL NOT BE REQUIRED | | IN OCCUPANCIES IN WHICH 15 OR LESS PEOPLE ARE EMPLOYED. | | 3. SEPARATE FACILITIES SHALL NOT BE REQUIRED FOR FOOD | | SERVICE ESTABLISHMENTS WHICH SEAT 10 PERSONS OR LESS. | | 4. SEPARATE FACILITIES SHALL NOT BE REQUIRED IN | | BUSINESS AND MERCANTILE OCCUPANCIES WITH A TOTAL FLOOR | | AREA OF 3,000 SQUARE FEET (279 M2) OR LESS. | | | | 3. THE WOMENS ROOM #104 HAS A UNISEX AREA INSIDE OF IT. | | FBC 2007 PLUMBING 403.7.2 UNISEX TOILET ROOMS. | | UNISEX TOILET ROOMS SHALL INCLUDE ONLY ONE WATER CLOSET | | AND ONLY ONE LAVATORY. A UNISEX BATHING ROOM IN | | ACCORDANCE WITH SECTION 403.7.3 SHALL BE CONSIDERED A | | UNISEX TOILET ROOM. | | EXCEPTION: A URINAL IS PERMITTED TO BE PROVIDED IN | | ADDITION TO THE WATER CLOSET IN A UNISEX TOILET ROOM. | | | | REVIEW BY LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | (561) 805-6692 | | FAX (561) 653-2692 | | E-MAIL [email protected] | | | | | | | | | | |
|