2010-04-22 13:51:16REVIEW ACTION: DENIED
  
 1. FBC 2007 106.3.5 PLUMBING SANITARY AND WATER PIPE
 ISOMETRICS REQUIRED.
  
 2. FBC 2007 PLUMBING 403.2 SEPARATE FACILITIES.
 WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE
 FACILITIES SHALL BE PROVIDED FOR EACH SEX.
 EXCEPTIONS:
 1. SEPARATE FACILITIES SHALL NOT BE REQUIRED FOR
 PRIVATE FACILITIES.
 2. SEPARATE EMPLOYEE FACILITIES SHALL NOT BE REQUIRED
 IN OCCUPANCIES IN WHICH 15 OR LESS PEOPLE ARE EMPLOYED.
 3. SEPARATE FACILITIES SHALL NOT BE REQUIRED FOR FOOD
 SERVICE ESTABLISHMENTS WHICH SEAT 10 PERSONS OR LESS.
 4. SEPARATE FACILITIES SHALL NOT BE REQUIRED IN
 BUSINESS AND MERCANTILE OCCUPANCIES WITH A TOTAL FLOOR
 AREA OF 3,000 SQUARE FEET (279 M2) OR LESS.
  
 3. THE WOMENS ROOM #104 HAS A UNISEX AREA INSIDE OF IT.
 FBC 2007 PLUMBING 403.7.2 UNISEX TOILET ROOMS.
 UNISEX TOILET ROOMS SHALL INCLUDE ONLY ONE WATER CLOSET
 AND ONLY ONE LAVATORY. A UNISEX BATHING ROOM IN
 ACCORDANCE WITH SECTION 403.7.3 SHALL BE CONSIDERED A
 UNISEX TOILET ROOM.
 EXCEPTION: A URINAL IS PERMITTED TO BE PROVIDED IN
 ADDITION TO THE WATER CLOSET IN A UNISEX TOILET ROOM.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  
  
  
  