Plan Review Notes
Plan Review Notes For Permit 10040264
Permit Number 10040264
Review Stop B
Sequence Number 1
Notes
Date Text
2010-04-20 13:06:26BUILDING PLAN REVIEW
 PERMIT: 10040264
 ADD: 624 NOTTINGHAM BLVD
 CONT: ABACOA CONSTRUCTION LLC
 TEL: (561)722-3890
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 DESIGN PROFESSIONAL: ARCHITECT MICHAEL HALL
 TEL: UNKNOWN
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A-1 MAIN ENTRANCE INDICATES A NEW ACCESSIBLE
 RAMP.
 1A) TOP LANDING IS TO SHORT, 11-4.8 .4(2) THE TOP
 LANDING TO BE A MINIMUM OF 5'-0" IN THE DIRECTION OF
 TRAVEL.
  
 1B) THE RAMP ITSELF IS INDICATED AS 6'-6" LONG
 REQUIRING HANDRAILS ON BOTH SIDES. 11.4.8.5. HANDRAILS:
 IF A RAMP HAS A RISE GREATER THAN 6" OR A HORIZONTAL
 PROJECTION GREATER THAN 72", THEN
 IT SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 1C) THE PLANS DO NOT PROVIDE A DIMENSION FOR THE BOTTOM
 LANDING, 11-4.8.4 (2) REQUIRES THE BOTTOM LANDING TO BE
 A MINIMUM OF 72" OF STRAIGHT AND LEVEL CLEARENCE.
  
 2) SHEET A-1 ALL OF THE OTHER ENTRANCES OR EXITS
 INDICATE A DROP MAKING THESE UN-ACCESSIBLE, SIGNAGE IS
 REQUIRED. SEE 11-4.1.3(8)(D) ENTRANCES WHICH ARE NOT
 ACCESSIBLE SHALL HAVE DIRECTIONAL SIGNAGE COMPLYING
 WITH SECTIONS 11-4.30.1, 11-4.30.2, 11-4.30.3, AND
 11-4.30.5, WHICH INDICATES THE LOCATION OF THE NEAREST
 ACCESSIBLE ENTRANCE.
  
 3) SHEET A-1 MEN'S RESTROOM DOOR# 16 IS MISSING THE 18"
 LATCH SIDE OF THE DOOR. 11-4.13.6 MANEUVERING
 CLEARENCES AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL
 BE AS SHOWN IN FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL.
  
 4) SHEET A-2 THE ROOF PRESSURES ARE LOW FOR 140 MPH,
 15' MEAN ROOF HEIGHT AND B EXPOSURE, 10 FT AREA, FOR A
 FLAT ROOF , 10 SQ FT:
 ZONE ONE +14.3/ -35.3
 ZONE TWO +14.3/ -59.2
 ZONE THREE +14.3/-89.0
  
 5) PLANS INDICATE THE FLAT ROOF IS TO BE REPLACED WITH
 MODIFIED BITUMEN, NO PRODUCT APPROVALS WERE SUBMITTED,
 WHEN SUBMITTED PLEASE INDICATE TYPE OF ROOF INSULATION
 WITH SYSTEM.
 RULE 9B-72 (31) ( D)
  
 6) WINDOW AND DOOR PRODUCT APPROVALS ARE TO BE REVIEWED
 BY THE DESIGN PROFESSIONAL, 106.3.3 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 7) ARCH FG-4500 STOREFRONT SYSTEM WAS SUBMITTED BUT
 THTE PLANS DO NOT INDICATE WHERE THIS UNIT IS TO BE
 INSTALLED. 106.1.2. ADDITIONAL INFORMATION REQUIRED.
  
 8) THE ELEVATIONS INDICATE WITHIN THE EXTERIOR WALL
 GLASS BLOCK WINDOWS AS WELL AS A-3 WINDOW SCHEDULE
 WINDOW TYPE "H". RULE 9B-72 (31)(B) WILL REQUIRE
 PRODUCT APPROVAL.
  
 9) THE MASONITE PRODUCT APPROVAL PLEASE HIGHLIGHT WHICH
 OF THESE PRODUCT ARE GOING TO BE INSTALLED SINCE EACH
 MODEL HAS DIFFERENT POSITIVE & NEGATIVE PRESSURES.
  
 10) SHEET M-1 NOTE #20 INDICATES THE NEW A/C CONDENSING
 UNITS ARE TO SIT ON THE EXISTING ROOF CURBS. PLEASE
 NOTE MECH. 301.12 WIND RESISTANCE MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES
 ON THE EQUIPMENT & THE SUPPORTS AS DETERMINED IN
 ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMPLISHED BY
 DESIGN OR BY APPLICATION OF SECTION 301.12.1.
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO