2010-06-16 09:18:59 | BUILDING PLAN REVIEW |
| PERMIT: 10040228 |
| ADD: 301 N OLIVE AVE. |
| CONT: CATALFUMO |
| TEL: (561)308-9709 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| JUNE 16/ 2010 |
| |
| BRPH ARCHITECTS, ENGINEERS, CONSTRUCTORS |
| TEL: 561-616-5878 |
| ARCH: LEILA ROUADY AR 94061 |
| STRUC. ENG. ROBERT BROWN FL PE 56928 |
| |
| 2ND REVIEW |
| ACTION: 6/22/2010 COMPLIED |
| 1) COMPLIED. |
| |
| 2)COMPLIED, PROVISO: 6/22/2010 I'VE MET WITH THE |
| ARCHITECT MS LEILA ROUADY, AND CONTRACTOR CATALFUMO |
| TODAY AND A NEW COVERSHEET WILL BE ISSUED WITH THE |
| CORRECT ADDRESS AND PCN, THEY WILL BE SUBMITTED THIS |
| AFTERNOON BY ROBERT KUMMER. PLANS AND THE PERMIT |
| APPLICATION INDICATE THE WORK TO BE COMPLETED UNDER 301 |
| N OLIVE (PCN 74-43-43-22-12-008-0010) THE PLANS |
| ACTUALLY INDICATE THE WORK (BUILDING TO BE BUILT) TO BE |
| LOCATED AT 215 N OLIVE (PCN 74-43-43-21-01-053-0000) |
| JUST EAST OF THE PARKING GARAGE, PLEASE CORRECT THE |
| PERMIT APPLICATION AS WELL AS PLANS. PLEASE REVIEW PALM |
| BEACH COUNTY PROPERTY APPRAISERS OFFICE WEB SITE AND |
| PROPERTY CONTROL NUMBERS. THERE IS POSSIBLY A UNITY OF |
| TITLE ADJOINING THESE LOTS ALSO THAT WAS NEVER RECORDED |
| AT THE PROPERTY APPRAISERS OFFICE! |
| |
| 3)6/22/2010 COMPLIED TODAYS MEETING WITH ARCITECT |
| INDICATED FOOTNOTE "I" TABLE 704.8 OPENINGS TO BE |
| UNLIMITED/ UNPROTECTED OPENINGS. |
| PLEASE PROVIDE A PROPOSED PROPERTY LINE BETWEEN THE |
| EAST SIDE OF THE PARKING GARAGE AND THEWEST SIDE OF THE |
| NEW CHILLER BUILDING WITH CODE CORRECT OPENING |
| PROTECTIVE???S IN COMPLIANCE WITH TABLE 704.8, OR IS |
| THIS DESIGN TO COMPLY WITH FBC-B 503.1.2 BUILDINGS ON |
| THE SAME LOT. NOTE THIS BUILDING IS DESIGNED AS A TYPE |
| II-B UNPROTECTED/ NON-SPRINKLERED BUILDING. THE |
| RESPONCE TO THIS COMMENT DOES NOT PROVIDE THE LOCATION |
| OF THE ASSUMED PROPERTY LINE, NOR DOES THE DESIGN TEAM |
| PROVIDE THE PERCENTAGE OF OPENINGS ON THE EAST SIDE OF |
| THE PARKING GARAGE. THE THIRD ISSUE IS THE DESISGN TEAM |
| INDICATES THE THE OPENING PERCENTAGE OF 6%. SHEET A-200 |
| INDICATES FLOOR TO CEILING 1,054 SQ FT WITH 381 SQ FT |
| OF OPENINGS OR APPROXIMATELY 36% OF OPENINGS. |
| |
| 4)6/22/2010 COMPLIED TODAYS MEETING WITH ARCHITECT |
| TABLE 602TYPE IIB BUILDING NOT TO REQUIRE RATED WALLS |
| 10-15 FEET. |
| SHEET A-101 INDICATES UNDER THE HEADING FIRE RESISTANCE |
| RATINGS PER TABLE 601 BUT NO MENTION OF FIRE RESISTANCE |
| RATINGS REQUIRED PER TABLE 602, PLEASE PROVIDE THE |
| DISTANCE TO THE NORTH PROPERTY LINE AND ALSO TO THE |
| WEST FOR AN ASSUMED PROPERTY LINE IF NOT TO BE |
| CONSIDERED A SINGLE BUILDING PER FBC-B 503.1.2. THE |
| NORTH PROPERTY LINE WALL IS INDICATED AS TEN FT AWAY |
| FROM THE PROPERTY LINE, FOR A TYPE IIB BUILDING TABLE |
| 602 REQUIRING THE WALL TO BE 1 HR. THE WEST WALL IS A |
| BEARING WALL DEPENDING ON THE LOCATION OF THE WEST |
| ASSUMED PROPERTY LINE BETWEEN BUILDINGS TABLE 601 |
| FOOTNOTEG AND TABLE 602. |
| |
| 5) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| PROVIDE 2 COPIES, |
| 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING |
| REPORTS, MISSING REPORTS ARE AS FOLLOWS: |
| 5A) COMPLIED. |
| 5B) EXTERIOR COILING DOOR- SEE SUBMITTED REPORT 2211.3 |
| (HIGHLIGHTED) DOORS FOR VARIOUS OPENING SIZES ARE RATED |
| FOR VARIOUS DESIGN WIND LOADS, (SEE EVALUATION REPORT), |
| PLEASE INDICATE WHICH SUB-SYSTEM WITH ASSOCIATED |
| PRESSURES. 6/21/10 COMPLIED E-MAIL SENT INDICATING FL |
| 2211.3. |
| 5C) COMPLIED. |
| 5D) ROOF ASSEMBLY PLEASE CIRCLE WHICH SUBSYSTEM TO BE |
| INSTALLED, WITH ASSOCIATED PRESSURES. COMPLIED, NOA |
| 07-0228.07 PAGE 23 OF 38 MAXIMUM DESIGN PRESSURE OF -75 |
| PSF LIMITATION #7 , ENHANCED FASTENING NOT REQUIRED |
| 3'-0" PARPET AND HIGHER NO ZONE THREE.N |
| 5F) COMPLIED. |
| |
| |
| 6-10) COMPLIED. |
| |
| 11) COMPLIED. |
| |
| 12) COMPLIED. |
| |
| 13) SHEET A-301 INDICATES THE USE OF EFIS TRIM WILL |
| NEED PROFILE AND ADHESIVE. 6/21/10 E-MAIL WITH EFIS |
| TRRIM ADHESIVE ATTACHMENT, COMPLIED. |
| |
| 14) NOTE: AWNING PERMITS TO BE UNDER SEPARATE PERMIT! |
| |
| A MEETING WOULD BE SUGGESTED WITH THE DESIGN TEAM AND |
| CONTRACTOR BEFORE THE PLANS ARE RESUBMITTED TO VERIFY |
| ALL COMMENTS WERE SATISFIED SO A PERMIT CAN BE ISSUED |
| IN A TIMELY MATTER! THANKS FOR ALL YOUR COOPERATION |
| WITH THIS MATTER. |
| |
| JIM WITMER C. B. O. |
| COMMERCIAL COMBINATION PLAN REVIEW |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| |
| PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| CUSTOMER SERVICE SURVEY AT: |
| WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953JIM WITMER |
| C. B. O. |
| COMMERCIAL COMBINATION PLAN REVIEW |