2010-05-20 16:35:50 | PALM BEACH COUNTY PROPOSED CHILLER BUILDING |
| PERMIT NUMBER 10040228 |
| |
| |
| 1. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE |
| ALARM SYSTEM. |
| |
| 2. THE KNOX-BOX CAN BE ORDERED AT WWW.KNOX-BOX.COM. |
| |
| 3. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. |
| |
| 4. PORTABLE FIRE EXTINGUISHERS SHOWN ON PAGE A-101 |
| SHALL BE OF SUITABLE SIZE AND RATING AND BE PROPERLY |
| SERVICE TAGGED. |
| |
| 5. PROPER SAFETY MEASURES SHALL BE TAKEN WHEN |
| EXCAVATING OR SAWCUTTING ACTIVITIES OCCUR AT THE SITE. |
| |
| 6. PROPER SAFETY MEASURES SHALL OCCUR WHEN USING ANY |
| GASOLINE POWERED EQUIPMENT INSIDE THE BUILDING FOR |
| SAWCUTTING PURPOSES TO AVOID THE BUILD-UP OF CARBON |
| MONOXIDE (CO) CARBON MONOXIDE IS AN ODORLESS, COLORLESS |
| GAS AND CAN BE FLAMMABLE IN THE PROPER CONCENTRATION. |
| PROPER VENTILATION CONTROLS SHALL BE PROVIDED. |
| |
| 7. KEYS FOR THE GENERATOR ENCLOSURE SHALL BE PLACED |
| INTO THE KNOX-BOX. |
| |
| 8. A SEPARATE PLAN AND PERMIT REQUIRED FOR THE |
| DEMOLITION OF ROOFTOP EQUIPMENT LOCATED AT THE |
| GOVERNMENTAL CENTER. |
| |
| 9. PLEASE INDICATE STRENGTH REQUIREMENTS FOR THE RAILS. |
| |
| 10. PLEASE REVIEW NFPA 214 FOR THE STANDARD FOR COOLING |
| TOWERS. |
| |
| 11. HOW LONG WILL THE TEMPORARY GENERATOR THAT WILL |
| PROVIDE EMERGENCY POWER BE ON SITE. HOW AND WHEN WILL |
| IT BE INSPECTED AND TESTED TO ENSURE PROPER FUNCTION. |
| |
| 12. COULD NOT LOCATE ANY EMERGENCY LIGHTING EQUIPMENT. |
| PLEASE INDICATE HOURS OF PROBABLE OCCUPANCY, |
| INSPECTION, OR SERVICE. |
| |
| |
| DENIED |
| |
| |
| MIKE CARSILLO, BATTALION CHIEF |
| BUREAU OF FIRE PREVENTION |
| 804-4709 PHONE |