Plan Review Notes
Plan Review Notes For Permit 10040228
Permit Number 10040228
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-05-20 16:35:50PALM BEACH COUNTY PROPOSED CHILLER BUILDING
 PERMIT NUMBER 10040228
  
  
 1. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE
 ALARM SYSTEM.
  
 2. THE KNOX-BOX CAN BE ORDERED AT WWW.KNOX-BOX.COM.
  
 3. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 4. PORTABLE FIRE EXTINGUISHERS SHOWN ON PAGE A-101
 SHALL BE OF SUITABLE SIZE AND RATING AND BE PROPERLY
 SERVICE TAGGED.
  
 5. PROPER SAFETY MEASURES SHALL BE TAKEN WHEN
 EXCAVATING OR SAWCUTTING ACTIVITIES OCCUR AT THE SITE.
  
 6. PROPER SAFETY MEASURES SHALL OCCUR WHEN USING ANY
 GASOLINE POWERED EQUIPMENT INSIDE THE BUILDING FOR
 SAWCUTTING PURPOSES TO AVOID THE BUILD-UP OF CARBON
 MONOXIDE (CO) CARBON MONOXIDE IS AN ODORLESS, COLORLESS
 GAS AND CAN BE FLAMMABLE IN THE PROPER CONCENTRATION.
 PROPER VENTILATION CONTROLS SHALL BE PROVIDED.
  
 7. KEYS FOR THE GENERATOR ENCLOSURE SHALL BE PLACED
 INTO THE KNOX-BOX.
  
 8. A SEPARATE PLAN AND PERMIT REQUIRED FOR THE
 DEMOLITION OF ROOFTOP EQUIPMENT LOCATED AT THE
 GOVERNMENTAL CENTER.
  
 9. PLEASE INDICATE STRENGTH REQUIREMENTS FOR THE RAILS.
  
 10. PLEASE REVIEW NFPA 214 FOR THE STANDARD FOR COOLING
 TOWERS.
  
 11. HOW LONG WILL THE TEMPORARY GENERATOR THAT WILL
 PROVIDE EMERGENCY POWER BE ON SITE. HOW AND WHEN WILL
 IT BE INSPECTED AND TESTED TO ENSURE PROPER FUNCTION.
  
 12. COULD NOT LOCATE ANY EMERGENCY LIGHTING EQUIPMENT.
 PLEASE INDICATE HOURS OF PROBABLE OCCUPANCY,
 INSPECTION, OR SERVICE.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX