Plan Review Notes
Plan Review Notes For Permit 10040228
Permit Number 10040228
Review Stop ENG
Sequence Number 1
Notes
Date Text
2010-05-19 12:02:32FAIL STATUS COMMENTS
  
 #1
 AS PER ORDENANCE NO. 4060-07 ALL DEMOLITION AND NEW
 CONSTRUCTION PERMITS SHALL SUBMIT A STORMWATER
 POLLUTION PREVENTION PLAN (SWPPP)
 EROSION CONTROL AND LAND STABILIZATION BOND IS
 REQUIRED.
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
 POLLUTION PREVENTION PLAN MUST SHOW THE PROPTECTION OF
 UTILITY EASEMENT WHERE WATER AND SEWER LINES ARE
 LOCATED.
 PLEASE CONTACT BRIAN MOREE AT ENGINEERING SERVICES
 DEPARTMENT FOR INFORMATION (561) 494-1098.
  
 A COPY OF THE ORDINANCE NO. 4060-07 MAY BE OBTAINED
 FROM THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR
 CITY HALL.
  
 #2 SUPPLY PURPOSE OF NEW SEWER LATERAL CONNECTION.
 PLUMBING PLANS THAT IS MADE REFERENCE TO WHERE NOT
 INCLUDED.
  
 #3 MAKE-UP WATER WILL REQUIRE A WATER CONNECTION, "NO
 SADDLES" DIRECT TAP ONLY, YOU WILL NEED A 1 1/2"X2"
 CORPORATION.
 NEEDED DEMAND IS 40 GPM (GALLONS PER MINUTE) HOWEVER WE
 NEED THE "PUMP INFORMATION" DEMAND.
 NOTE: AWWA SAYS 1" METER EQUAL TO 25-50 GPM (HEAD LOSS
 UP TO 15PSI) - 25 GPM MAX
 BADGER MODEL 120 (1 1/2")= AVERAGE GPM 80 GPM MAX
 CONTINUOUS OPERATION (RCDL DISC 1-1/2" FLGD)
 (15 PSI MAX FLOW LOSS) AWWA SAYS 100GPM TO 120GPM.
  
 #4 PHASE 1B FUTURE PUBLIC PAVILION IS NOT PART OF THIS
 PERMIT.
  
 #5 SUPPLY SIESMIC DESIGN AND OR VIBRATION ISOLATION
 EXPLANATION OF CHILLER BUILDING AS TO THE HARM OF
 EXISTING UNDERGROUND UTILITIES, THIS INCLUDES THE CLAY
 SEWER MAIN AND THE CAT IRON WATERMAIN.
  
 #6 CIVIL PLAN C-103 SHOWS CONFLICTS BUT "PROPOSED DATA
 CONDUIT" IS NOT DISPLAYED IN THE "CROSSING TABLE".
  
 #7 WATERMAIN DEPTH IS DISPLAYED AT 4' DEEP, HAS THIS
 INFORMATION BEEN VERIFIED IN THE FIELD?
  
 #8 ITEM 1-24 ON SHEET C-103 WAS NOT SHOWN OR IS CALLED
 OUT TWICE. REVIEW IN "DETAIL A - SITE IMPROVEMENT PLAN"
 SHEET C-103
  
 #9 RIM ELEVATION OF CATCH BASINS AND SANITARY SEWER
 MANHOLES IN THE AREA APEAR TO BE 12.20 +/-, YOUR FFE IS
 12.50. 6" ABOVE THESE FEATURES MINIMUM TO ALLOY VISUAL
 OVERFLOW BEFORE
 IT BACKS UP INTO THE BUILDING.
  
 #10 SUPPLY ADDRESS TO THIS NEW CHILLER BUILDING TO
 QUOTE THE NEW WATER AND SEWER FEES.
  
 MANUEL JULIAN GONZALEZ
 CSD ENGINEERING REVIEW
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved