Plan Review Notes For Permit 10040222 |
Permit Number |
10040222 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2010-05-07 09:03:14 | *****UNSAT***** | | | | 1) STANDARD SPRAY SPRINKLERS IN OPEN OFFICE AREA SPACED | | GREATER THAN 15'-0" APART. | | | | 2) PROVIDE MINIMUM PUMP SUCTION PRESSURE OF 20 PSI | | (HYDRAULIC CALCULATIONS). | | | | 3) HYDRAULIC CALCULATION BRANCH LINE LENGTH NOT PER | | NFPA. | | NODES 107 AND 102 ARE BEYOND THE 36' BRANCH LINE LENGTH | | AND SHOULD NOT BE CALCULATED. | | REVISE CALCULATED AREA EXCLUDING NODES 107 AND 102. | | | | | | WESLEY JOLIN | | FIRE PROTECTION ENGINEER | | 561.805.6730 | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561.805.6722 |
|