Plan Review Notes For Permit 10040209 |
Permit Number |
10040209 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-04-23 09:26:48 | | | 222 LAKEVIEW AVENUE, SUITE 120 | | PERMIT NUMBER 10040209 | | | | 1. NO FIRE SPRINKLER DETAILS PROVIDED. NO INFORMATION | | ON EXISTING OR NEW FIRE SPRINKLER HEADS. SEPARATE PLANS | | AND PERMITS REQUIRED FOR ANY FIRE SPRINKLER SYSTEM | | REMODELING. | | | | 2. NO FIRE ALARM DETAILS PROVIDED. NO INFORMATION ON | | EXISTING OR NEW FIRE ALARM EQUIPMENT. SEPARATE PLANS | | AND PERMITS REQUIRED FOR ANY FIRE ALARM SYSTEM | | REMODELING. | | | | 3. NEW FIRE RATED WALLS ARE TO BE PROPERLY IDENTIFIED | | AND ALL OPENINGS PROTECTED. NEW WALLS ARE TO BE | | LABELED. | | | | 4. NO EMERGENCY LIGTHING CONTAINED IN LARGE RESTROOMS. | | | | 5. TACTILE SIGNAGE REQUIRED AT EXIT DOORS. | | | | 6. ALL NEW FIRE DAMPERS SHALL BE DROP TESTED TO ENSURE | | PROPER OPERATION. | | | | DENIED | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | (561) 804-4724 PHONE | | (561) 804-4774 FAX |
|