2010-04-23 09:26:48 
 222 LAKEVIEW AVENUE, SUITE 120
 PERMIT NUMBER 10040209
  
 1. NO FIRE SPRINKLER DETAILS PROVIDED. NO INFORMATION
 ON EXISTING OR NEW FIRE SPRINKLER HEADS. SEPARATE PLANS
 AND PERMITS REQUIRED FOR ANY FIRE SPRINKLER SYSTEM
 REMODELING.
  
 2. NO FIRE ALARM DETAILS PROVIDED. NO INFORMATION ON
 EXISTING OR NEW FIRE ALARM EQUIPMENT. SEPARATE PLANS
 AND PERMITS REQUIRED FOR ANY FIRE ALARM SYSTEM
 REMODELING.
  
 3. NEW FIRE RATED WALLS ARE TO BE PROPERLY IDENTIFIED
 AND ALL OPENINGS PROTECTED. NEW WALLS ARE TO BE
 LABELED.
  
 4. NO EMERGENCY LIGTHING CONTAINED IN LARGE RESTROOMS.
  
 5. TACTILE SIGNAGE REQUIRED AT EXIT DOORS.
  
 6. ALL NEW FIRE DAMPERS SHALL BE DROP TESTED TO ENSURE
 PROPER OPERATION.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4724 PHONE
 (561) 804-4774 FAX