2010-04-19 14:19:42BUILDING PLAN REVIEW
 PERMIT: 10040209
 ADD: 222 LAKEVIEW AVE #120
 CONT: HOLT LEE CONSTRUCTION
 TEL: (954)270-1894
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A1.1 NOTE #1 INDICATES THE STORE FRONT WINDOWS
 WILL BE REPLACED AND BUILDING HAS HURRICANE SHUTTERS.
  
 1A) PLEASE PROVIDE PRODUCT APPROVALS FOR STOREFRONT
 WINDOWS , 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 1B) PLEASE INDICATE HOW THE EXISTING HURRICANE SHUTTERS
 MEET TODAY???S STANDARDS WHEN WERE THEY PERMITTED? AN
 ENGINEERS REPORT ANALYZING TYPE OF SHUTTER OR PANEL
 SYSTEM GAUGE OF METAL, FASTENER SPACING WITH A CURRENT
 FLORIDA APPROVAL OR MIAMI-DADE NOA WOULD BE ACCEPTABLE.
 104.11 ALTERNATE MATERIALS, DESIGN AND METHODS OF
 CONSTRUCTION AND EQUIPMENT.
  
 2) SHEET A1.1 TENANT SEPARATION WALLS:
 2A) DOOR #1 THE MAIN ENTRY DOOR NOTE ON A3.2 INDICATES
 RATED DOUBLE ENTRY DOORS TO MATCH EXISTING STORE FRONT
 SYSTEM. IS THE EXISTING STOREFRONT DOORS AND SIDE
 LIGHTS TO REMAIN? 106. 1.2 ADDITIONAL INFORMATION
 REQUIRED, THESE DOORS ARE LOCATED WITHIN A 1 HR TENANT
 SEPARATION WALL.
  
 2B) SHEET A1.1 WINDOW #102 WILL ALSO NEED TO PROVIDE
 FIRE RATING SINCE IT IS LOCATED WITHIN A 1 HOUR TENANT
 SEPARATION WALL. SEE TABLE 715.4.
  
 2C) THERE IS A ONE HOUR WALL BETWEEN STORAGE ROOM #1
 AND THE GYM, ARE THE TWO STORAGE ROOMS UNDER SEPARATE
 TENANCY REQUIRING A ONE HOUR TENANT SEPARATION.
 708.1(7).
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved