Plan Review Notes For Permit 10040177 |
Permit Number |
10040177 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-04-12 08:01:42 | THE PULL TAS 105-98 TEST RESULTS AND PLANS SHOWING | | RE-LOCATED ROOF HATCH WERE SUBMITTED, AS REQUESTED. | | | | 1) THE REVISED LOCATION OF THE ROOF HATCH TO ROOF ZONE | | 1 IS CODE COMPLIANT. | | | | 2) THE FASTENER WITHDRAWL RESISTANCE TEST REPORT IS | | INCOMPLETE AND HAS BEEN DENIED. | | | | THE FOLLOWING INFORMATION IS REQUIRED FOR THE TAS | | 105-98 REPORT. | | | | - THE CERTIFICATION OF THE DYNAMETER CALABRATION WITHIN | | 3 MONTHS OF THE FIELD TEST DATE WAS NOT SUBMITTED. TAS | | 105-98 (10.1.1) | | | | - THE DECK SUBSTRATE TESTED WAS NOT SPECIFIED. TAS | | 105-98 (10.1.3) | | | | - THE FASTENER TYPE AND MANUFACTURER IS NOT SPECIFIC | | AND THE ROOFING COMPONENT TO BE SECURED IS NOT | | SPECIFIED. TAS 105-98 (10.1.4) | | | | - THE SPEED OF THE INSTALLATION TOOL AND LITERATURE ON | | THE FASTENING DEVICE WAS NOT PROVIDED. TAS 105-98 | | (10.1.7) | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|