Plan Review Notes For Permit 10040170 |
Permit Number |
10040170 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-04-07 16:49:46 | RE-ROOF BUILDING REVIEW CHECKLIST. | | 2007 FBC WITH 2009 REVISIONS. | | | | 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS | | REQUIRED BY GENERAL LIMITATION #7 TO MEET THE DESIGN | | PRESSURES OF SEC. 1609 FBC 2007 AT PERIMETER AND CORNER | | AREAS. | | ***NOTE: DESIGN PROFESSIONAL DOING THE RAS 117 | | CALCULATIONS TO TAKE INTO CONSIDERATION THAT ACCORDING | | TO THE 2009 REVISIONS THIS BUILDING IS LOCATED ON | | EXPOSURE "C". | | | | 2- PERMIT VALUATION IS TOO LOW. SEC. 108.3 CITY | | AMENDMENTS TO FBC. OWES $48.48 FOR UPDATED VALUATION. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|