2010-04-07 16:49:46RE-ROOF BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 TO MEET THE DESIGN
 PRESSURES OF SEC. 1609 FBC 2007 AT PERIMETER AND CORNER
 AREAS.
 ***NOTE: DESIGN PROFESSIONAL DOING THE RAS 117
 CALCULATIONS TO TAKE INTO CONSIDERATION THAT ACCORDING
 TO THE 2009 REVISIONS THIS BUILDING IS LOCATED ON
 EXPOSURE "C".
  
 2- PERMIT VALUATION IS TOO LOW. SEC. 108.3 CITY
 AMENDMENTS TO FBC. OWES $48.48 FOR UPDATED VALUATION.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712