Plan Review Notes
Plan Review Notes For Permit 10040086
Permit Number 10040086
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-04-07 16:45:24*****DENIED*****
  
  
 1. VERIFY THE SPRINKLER COUNT. IT APPEARS TO BE MORE
 THAN THE 39 WHICH IS INDICATED IN THE SPRINKLER LEGEND.
  
 2. THE PLAN CONTAINS THE NAME AND LICENSE NUMBER OF A
 PROFESSIONAL ENGINEER; THEREFORE HIS SEAL AND SIGNATURE
 WILL BE REQUIRED OR REMOVE THE THE STAMP OF THE
 ENGINEER FROM THE PLAN.
  
 3. PROVIDE SPEC SHEETS FOR NEW PIPING. SPRINKLER HEADS,
 ETC.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722