2010-04-06 13:43:41 | BUILDING PLAN REVIEW |
| PERMIT: 10040029 |
| ADD: 1801 S FLAGLER# 1404 |
| CONT: PHILIP E. JOHNSON, INC. |
| TEL: (561)662-8656 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| BUILDING APPROVED WITH EXCEPTION! |
| THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| ASSESSMENT OF RE-INSPECTION FEE(S). |
| |
| |
| 1) MISSING INFORMATION ON STRUCTURE-BORNE SOUND |
| INSULATION. |
| 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES |
| BETWEEN DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A |
| PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE |
| AN IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS |
| THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE |
| WITH ASTM E 492. |
| |
| 2) 603.1 ALLOWABLE MATERIALS. COMBUSTIBLE MATERIALS |
| SHALL BE PERMITTED IN BUILDINGS OF TYPE I OR TYPE II |
| CONSTRUCTION IN THE FOLLOWING APPLICATIONS AND IN |
| ACCORDANCE WITH SECTIONS 603.1.1 THROUGH 603.1.3: |
| |
| 1. FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN: |
| |
| 1.1. NONBEARING PARTITIONS WHERE THE REQUIRED |
| FIRE-RESISTANCE RATING IS 2 HOURS OR LESS. |
| |
| JIM WITMER C. B. O. |
| COMMERCIAL COMBINATION PLAN REVIEW |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| |