Plan Review Notes
Plan Review Notes For Permit 10040017
Permit Number 10040017
Review Stop B
Sequence Number 1
Notes
Date Text
2010-04-05 10:11:14RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 07-1203.01 SUBMITTED. NEED TO MEET THE DESIGN PRESSURES
 OF SEC. R301 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 2- FLAT ROOF NOA 07-1203.01 SUBMITTED WAS SUPERSEDED.
 SEE MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA.
  
 3- DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS
 TO TAKE INTO CONSIDERATION THAT ACCORDING TO SEC.
 R301.2.1.4.3 OF 2009 REVISIONS TO THE 2007 FLORIDA
 RESIDENTIAL CODE THIS BUILDING IS LOCATED ON EXPOSURE
 "C" NOT "B".
  
 4- SHINGLES NOA 07-1120.15 SUBMITTED WAS SUPERSEDED.
 SEE MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA.
  
 5- NAIL ENHANCING LETTER IS REFERRING TO PERMIT
 #09040586. THIS PERMIT IS FOR ANOTHER ADDRESS NOT FOR
 1018 PARK CIRCLE S. REVISE AS REQUIRED.
 NOTE: THIS LETTER CAN ONLY BE USED WHEN THE NOA DOESN'T
 REQUIRE SIGNED AND SEALED RAS 117 CALCULATIONS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712