Plan Review Notes For Permit 10040017 |
Permit Number |
10040017 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-04-05 10:11:14 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | 07-1203.01 SUBMITTED. NEED TO MEET THE DESIGN PRESSURES | | OF SEC. R301 OF 2007 FLORIDA RESIDENTIAL CODE. | | | | 2- FLAT ROOF NOA 07-1203.01 SUBMITTED WAS SUPERSEDED. | | SEE MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA. | | | | 3- DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS | | TO TAKE INTO CONSIDERATION THAT ACCORDING TO SEC. | | R301.2.1.4.3 OF 2009 REVISIONS TO THE 2007 FLORIDA | | RESIDENTIAL CODE THIS BUILDING IS LOCATED ON EXPOSURE | | "C" NOT "B". | | | | 4- SHINGLES NOA 07-1120.15 SUBMITTED WAS SUPERSEDED. | | SEE MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA. | | | | 5- NAIL ENHANCING LETTER IS REFERRING TO PERMIT | | #09040586. THIS PERMIT IS FOR ANOTHER ADDRESS NOT FOR | | 1018 PARK CIRCLE S. REVISE AS REQUIRED. | | NOTE: THIS LETTER CAN ONLY BE USED WHEN THE NOA DOESN'T | | REQUIRE SIGNED AND SEALED RAS 117 CALCULATIONS. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|