Plan Review Notes For Permit 10030823 |
Permit Number |
10030823 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-04-01 14:05:14 | | | | | 701 SOUTH OLIVE AVENUE | | PERMIT NUMBER 10030823 | | | | | | 1. CONFERENCE ROOM 101 REQUIRES SPRINKLER PROTECTION | | BELOW THE 8" WIDE SOFFIT WHEN UTILIZING SIDEWALL | | SPRINKLERS FOR PROTECTION. | | | | 2. IT APPEARS THAT THE WRONG TYPE OF FIRE SPRINKLER | | HEADS ARE BEING USED. IT APPEARS THE SPACE WILL NO | | LONGER BE RESIDENTIAL BUT OFFICE SPACE. THE HEADS SHOWN | | HAVE A LOWER K FACTOR. PLEASE EXPLAIN RATIONALE FOR THE | | CONTINUED USE OF RESIDENTIAL SPRINKLERS IN THIS OFFICE | | SPACE. | | | | | | DENIED | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | (561) 804-4709 PHONE | | (561) 804-4774 FAX | | | | WESLEY JOLIN, FIRE PROTECTION ENGINEER | | BUREAU OF FIRE PREVENTION | | (561) 805-6730 PHONE | | (561) 804-4774 FAX |
|