Plan Review Notes
Plan Review Notes For Permit 10030823
Permit Number 10030823
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-04-01 14:05:14 
  
 701 SOUTH OLIVE AVENUE
 PERMIT NUMBER 10030823
  
  
 1. CONFERENCE ROOM 101 REQUIRES SPRINKLER PROTECTION
 BELOW THE 8" WIDE SOFFIT WHEN UTILIZING SIDEWALL
 SPRINKLERS FOR PROTECTION.
  
 2. IT APPEARS THAT THE WRONG TYPE OF FIRE SPRINKLER
 HEADS ARE BEING USED. IT APPEARS THE SPACE WILL NO
 LONGER BE RESIDENTIAL BUT OFFICE SPACE. THE HEADS SHOWN
 HAVE A LOWER K FACTOR. PLEASE EXPLAIN RATIONALE FOR THE
 CONTINUED USE OF RESIDENTIAL SPRINKLERS IN THIS OFFICE
 SPACE.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4709 PHONE
 (561) 804-4774 FAX
  
 WESLEY JOLIN, FIRE PROTECTION ENGINEER
 BUREAU OF FIRE PREVENTION
 (561) 805-6730 PHONE
 (561) 804-4774 FAX