Plan Review Notes For Permit 10030781 |
Permit Number |
10030781 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-04-06 15:46:28 | *************EXPEDITED**************** | | 2ND ROUND | 2010-03-31 13:18:45 | | | | | 701 SOUTH DIXIE HIGHWAY | | PERMIT NUMBER 10030781 | | | | | | 1. THE FLOOR PLANS ARE LABELED INCORRECTLY. THE FIRST | | FLOOR IS LABELED AS THE MEZZANINE AND THE MEZZANINE IS | | LABELED AS THE FIRST FLOOR. | | | | 2. NOTE # 16 IS INCORRECT. WHEN DUCT DETECTORS ARE | | ACTIVATED THEY SHALL ACTIVATE AN ALARM INSTEAD OF A | | SUPERVISORY SIGNAL PER LOCAL POLICY. | | | | | | DENIED | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | (561) 804-4724 PHONE | | (561) 804-4774 FAX |
|