2010-04-29 08:28:43 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY MECHANICAL | | | | 1) SOME OF THE SUPPLY DUCT SIZES ARE NOT SPECIFIED ON | | THE PLANS. PLEASE CORRECT. M1601 | | | | 2) THE SIZE OF THE TRANSFER DUCT FOR MASTER BEDROOM | | SUITE IS NOT SPECIFIED ON THE PLANS. PLEASE CORRECT. | | M1602.4 | | | | 3) PLEASE CHECK THE CFMS AT THE DROPS. SOME OF THEM | | APPEAR TO BE TOO LOW. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|