Date Text
2010-04-29 16:44:512007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) CHANGES WERE MADE TO THE SIGNED AND SEALED PLANS
 USING WHITE-OUT.
  
 2) ON DRAWINGS D-1 AND A-2 THE WRONG EDITIONS OF THE
 FLORIDA BUILDING CODE AND ASCE 7 ARE SPECIFIED. THE
 APPLICABLE BUILDING CODE IS THE 2007 FBC WITH 2009
 REVISIONS WHICH REFERENCES ASCE 7 - 05. PLEASE CORRECT.
  
 3) PLEASE UPDATE THE MASONRY STANDARDS THAT ARE
 SPECIFIED ON SHEET A3 TO CORRESPOND WITH THE EDITIONS
 THAT ARE REFERENCED BY THE 2007 FBC. ACI 530-05,
 ASCE5-05, ASTM C 270-04 ASTM A 615-04A, TMS 402-05 AND
 TMS 602-05.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714