Plan Review Notes For Permit 10030690 |
Permit Number |
10030690 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-04-28 13:34:35 | ELECTRICAL REVIEW 04/27/2010 | | | | 1. PROVIDE ESSENTIAL TASK LIGHING REQUIRED PURSUANT TO | | 517.33(A)(4) FOR X-RAY ROOM. | | 2. RELOCATE POWER SHUT-OFF CONTROL FOR X-RAY TO | | ADJACENT CONTROL STATION PURSUANT TO 517.72(B) | | 3. PLEASE REVIEW USE OF BREAKROOM RECEPTACLES WITH | | CLIENT. IF MICROWAVE(S) AND COFFEE EQUIPMENT ARE | | DESIRED ADDITIONAL CIRCUITS MAY BE INDICATED TO PREVENT | | NUISANCE TRIPPING OR OVERLOADING OF CIRCUITS. | | | | NOTE: IF DELAYS ARE ANTICIPATED IN CORRECTING THESE | | ISSUES WHICH MAY DETRIMENTALLY IMPACT THE PROJECT, A | | PROVISO OR PROVISOS MAY BE ISSUED TO ALLOW WORK TO | | BEGIN. | | | | PLEASE CONTACT ME WITH ANY QUESTIONS OR CONCERNS | | REGARDING THIS REVIEW. | | | | DOUG WISE | | 561-805-6650 | | [email protected] |
|