2010-04-19 16:23:06 | BUILDING PLAN REVIEW |
| PERMIT:10030690 |
| ADD: 525 OKEECHOBEE BLVD/ 14TH FLOOR |
| CONT: BALFOUR BEATTY CONST |
| TEL: (954) 248-0107 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) SHEET G0201 BUILDING CODE INFORMATION: PLEASE ADD |
| 2007 EXISTING BUILDING CODE, LEVEL OF ALTERATION 401.4 |
| A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A |
| COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| SECTIONS 403, 404 AND 405 OF THIS CODE. |
| |
| 2) SHEET G0201 BUILDING CODE NOTE #8 INDICATES FIRE |
| PROOFING OF WALLS AND FLOORS BUT MISSING DETAILS FOR |
| SUCH PENETRATIONS, |
| 712.3.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM. FIRE |
| -RESISTANCE-RATED WALLS |
| 712.4.1.1 THROUGH PENETRATIONS.HORIZONTAL ASSEMBLIES. |
| |
| 3) SHEET A0200 FLOOR PLAN X-RAY ROOM TO COMPLY WITH : |
| 435.5.1.3 PRIOR TO CONSTRUCTION, THE FLOOR PLANS AND |
| EQUIPMENT ARRANGEMENT OF ALL NEW INSTALLATIONS, OR |
| MODIFICATIONS OF EXISTING INSTALLATIONS, UTILIZING |
| X-RAY ENERGIES OF 200 KEV AND ABOVE FOR DIAGNOSTIC OR |
| THERAPEUTIC PURPOSES SHALL BE SUBMITTED TO THE |
| DEPARTMENT OF HEALTH FOR REVIEW AND APPROVAL. IN |
| COMPUTATION OF PROTECTIVE BARRIER REQUIREMENTS, THE |
| MAXIMUM ANTICIPATED WORKLOAD, USE FACTORS, OCCUPANCY |
| FACTORS AND THE POTENTIAL FOR RADIATION EXPOSURE FROM |
| OTHER SOURCES SHALL BE TAKEN INTO CONSIDERATION. |
| |
| 4) SHEET A0200 DOOR # 320B LEFT SIDE OF DOORWAY IT |
| APPEARS THAT TTHTE PLAN DOES NOT COMPLY WITH 11-4.13.6 |
| MANEUVERING CLEARENCES AT DOORS. MINIMUM MANEUVERING |
| CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC OR |
| POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE FLOOR |
| OR GROUND AREA WITHIN THE REQUIRED CLEARANCES SHALL BE |
| CLEAR & LEVEL. MINIMUM OF 18 INCHES. |
| |
| 5) SHEET M0700 EF-1 IT APPEARS TO BE A NEW ROOFTOP |
| EXHAUST FAN, MECH. 301.13 WIND RESISTANCE MECHANICAL |
| EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| PRESSURES ON THE EQUIPMENT & THE SUPPORTS AS DETERMINED |
| IN ACCORDANCE WITH THE FL BLD CODE. THIS MAY BE |
| ACCOMPLISHED BY DESIGN OR BY APPLICATION OF SECTION |
| 301.13.1. |
| |
| 1511.7 ROOF MOUNTED MECHANICAL UNIT S SHALL BE MOUNTED |
| ON CURBS RAISED A MINIMUM OF 8 INCHES ABOVE THE ROOF |
| SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE |
| UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM |
| CLEARENCE HEIGHT IN ACCORDANCE WITH TABLE 1511.7. |
| |
| INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| NOTICE. |
| |
| OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| - 5:00 PM. |
| |
| JIM WITMER C. B. O. |
| COMMERCIAL COMBINATION PLAN REVIEW |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| |
| PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| CUSTOMER SERVICE SURVEY AT: |
| WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |