2010-04-19 16:23:06BUILDING PLAN REVIEW
 PERMIT:10030690
 ADD: 525 OKEECHOBEE BLVD/ 14TH FLOOR
 CONT: BALFOUR BEATTY CONST
 TEL: (954) 248-0107
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET G0201 BUILDING CODE INFORMATION: PLEASE ADD
 2007 EXISTING BUILDING CODE, LEVEL OF ALTERATION 401.4
 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A
 COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 2) SHEET G0201 BUILDING CODE NOTE #8 INDICATES FIRE
 PROOFING OF WALLS AND FLOORS BUT MISSING DETAILS FOR
 SUCH PENETRATIONS,
 712.3.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM. FIRE
 -RESISTANCE-RATED WALLS
 712.4.1.1 THROUGH PENETRATIONS.HORIZONTAL ASSEMBLIES.
  
 3) SHEET A0200 FLOOR PLAN X-RAY ROOM TO COMPLY WITH :
 435.5.1.3 PRIOR TO CONSTRUCTION, THE FLOOR PLANS AND
 EQUIPMENT ARRANGEMENT OF ALL NEW INSTALLATIONS, OR
 MODIFICATIONS OF EXISTING INSTALLATIONS, UTILIZING
 X-RAY ENERGIES OF 200 KEV AND ABOVE FOR DIAGNOSTIC OR
 THERAPEUTIC PURPOSES SHALL BE SUBMITTED TO THE
 DEPARTMENT OF HEALTH FOR REVIEW AND APPROVAL. IN
 COMPUTATION OF PROTECTIVE BARRIER REQUIREMENTS, THE
 MAXIMUM ANTICIPATED WORKLOAD, USE FACTORS, OCCUPANCY
 FACTORS AND THE POTENTIAL FOR RADIATION EXPOSURE FROM
 OTHER SOURCES SHALL BE TAKEN INTO CONSIDERATION.
  
 4) SHEET A0200 DOOR # 320B LEFT SIDE OF DOORWAY IT
 APPEARS THAT TTHTE PLAN DOES NOT COMPLY WITH 11-4.13.6
 MANEUVERING CLEARENCES AT DOORS. MINIMUM MANEUVERING
 CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE FLOOR
 OR GROUND AREA WITHIN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL. MINIMUM OF 18 INCHES.
  
 5) SHEET M0700 EF-1 IT APPEARS TO BE A NEW ROOFTOP
 EXHAUST FAN, MECH. 301.13 WIND RESISTANCE MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT & THE SUPPORTS AS DETERMINED
 IN ACCORDANCE WITH THE FL BLD CODE. THIS MAY BE
 ACCOMPLISHED BY DESIGN OR BY APPLICATION OF SECTION
 301.13.1.
  
 1511.7 ROOF MOUNTED MECHANICAL UNIT S SHALL BE MOUNTED
 ON CURBS RAISED A MINIMUM OF 8 INCHES ABOVE THE ROOF
 SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE
 UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM
 CLEARENCE HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved