 3415 SOUTH DIXIE HIGHWAY
 PERMIT NUMBER 10030636
 FIRE SPRINKLER SYSTEM INSTALLATION FOR NEW TWO-STORY
 BUILDING
 WIGINTON FIRE SYSTEMS
  
  
 1. KNOX LOCKING CAPS NEEDED FOR THE FIRE DEPARTMENT
 CONNECTION (FDC) . BREAKAWAY CAPS ILLUSTRATED ON PAGE
 FP1.
  
 2. CHAIN AND LOCK REQUIRED ON BACKFLOW DEVICE IN
 ADDITION TO THE TAMPER SWITCHES.
  
 3. SITE PLAN DOES NOT ILLUSTRATE ANY NEW OR EXISTING
 FIRE HYDRANTS. THE FIRE DEPARTMENT CONNECTION (FDC)
 SHALL BE WITHIN 150 FEET OF A FIRE HYDRANT.
  
 4. WRONG EDITION OF NFPA 13 NOTED ON PAGE FP2. IT
 SHOULD READ NFPA 13, 2002 EDITION.
  
 5. ON PAGE FP2 AND FP3, 1 -1/4" BRANCH LINES NOT
 SUPPORTED BY HYDRAULIC CALCULATIONS.
  
 6. SEVEN FIRE SPRINKLERS LOCATED ON 36' OF BRANCH LINE
 ON FP2 OF THREE. THIS ARRANGEMENT IS NOT SUPPORTED BY
 THE HYDRAULIC CALCULATIONS.
  
 7. THE THREE FIRE SPRINKLER HEADS UNDERNEATH THE STAIRS
 ARE SUPPLIED BY A 1" PIPE. THIS ARRANGEMENT IS NOT
 SUPPORTED BY THE HYDRAULIC CALCULATIONS.
  
 8. ARCHITECTURAL ELEMENTS OR SOFFITS SHALL NOT
 INTERFERE WITH THE SPRAY PATTERN OF ANY FIRE SPRINKLER
 HEADS.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF