2010-04-19 16:18:032007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE LOCATION OF THE STRUCTURE PLACES IT IN EXPOSURE
 CATEGORY 'C' PER FBC R301.2.1.4.3. PLEASE CORRECT THE
 PLANS AND INCREASE THE COMPONENT AND CLADDING PRESSURES
 ACCORDINGLY.
  
 2) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 STRUCTURAL WINDOW MULLIONS THAT WILL BE USED PER DCA
 RULE 9B-72.
  
 3) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 4) THE ENERGY CALCULATION FORM DOES NOT SPECIFY THE NEW
 R-19 INSULATION THAT WILL BE INSTALLED TO THE SINGLE
 ASSEMBLY CEILING AREA. FBC N1104.AB.1
  