2010-03-25 13:54:05***** DENIED *****
  
 1) PROVIDE MEANS FOR ROOM IDENTIFICATION (ROOM NAME OR
 COLUMN BUBBLES ETC.).
  
 2) UPRIGHT SPRINKLER SYMBOL IS THE SAME SYMBOL AS THE
 BRANCH LINE OUTLET.
  
 3) FLEXIBLE SPRINKLER SYMBOL FROM KEY DOES NOT APPEAR
 ON THE FLOOR PLAN ANYWHERE.
  
 4) USE OF FLEXIBLE SPRINKLER CONNECTIONS NEED TO BE
 SUPPORTED BY HYDRAULIC SPRINKLER CALCULATIONS.
  
 5) SHOW LOCATION OF SYSTEM CONTROL VALVE.
  
 6) SHOW SIZE OF EXISTING CROSS MAIN.
  
 7) SHOW PIPE HANGER LOCATIONS.
  
 8) SOME EXISTING PIPING IS SHOWN IN GRAY WHILE OTHER
 EXISTING PIPING IS SHOWN IN BLACK.
  
 9) ROOM NORTH OF DINING ROOM DOES NOT PROVIDE PROPER
 SPRINKLER COVERAGE BELOW THE 10'-0" SOFFITS.
  
  