Plan Review Notes For Permit 10030555 |
Permit Number |
10030555 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-03-25 13:54:05 | ***** DENIED ***** | | | | 1) PROVIDE MEANS FOR ROOM IDENTIFICATION (ROOM NAME OR | | COLUMN BUBBLES ETC.). | | | | 2) UPRIGHT SPRINKLER SYMBOL IS THE SAME SYMBOL AS THE | | BRANCH LINE OUTLET. | | | | 3) FLEXIBLE SPRINKLER SYMBOL FROM KEY DOES NOT APPEAR | | ON THE FLOOR PLAN ANYWHERE. | | | | 4) USE OF FLEXIBLE SPRINKLER CONNECTIONS NEED TO BE | | SUPPORTED BY HYDRAULIC SPRINKLER CALCULATIONS. | | | | 5) SHOW LOCATION OF SYSTEM CONTROL VALVE. | | | | 6) SHOW SIZE OF EXISTING CROSS MAIN. | | | | 7) SHOW PIPE HANGER LOCATIONS. | | | | 8) SOME EXISTING PIPING IS SHOWN IN GRAY WHILE OTHER | | EXISTING PIPING IS SHOWN IN BLACK. | | | | 9) ROOM NORTH OF DINING ROOM DOES NOT PROVIDE PROPER | | SPRINKLER COVERAGE BELOW THE 10'-0" SOFFITS. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|