Plan Review Notes For Permit 10030552 |
Permit Number |
10030552 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-03-23 13:25:37 | ***** DENIED ***** | | | | | | 1) THE INFORMATION CONTAINED IN THE PROJECT DESCRIPTION | | DOES NOT CORRESPOND WITH WHAT IS SHOWN ON THE FLOOR | | PLAN. | | | | 2) FLOOR PLAN DOES NOT DISTINGUISH BETWEEN EXISTING | | DEVICES AND NEW DEVICES. | | | | 3) ONLY ONE SMOKE DETECTOR IS SHOWN IN THE FIRE ALARM | | RISER DIAGRAM WHEREAS, TWO SUCH DEVICES ARE SHOWN ON | | THE FLOOR PLAN. TO BETTER IDENTIFY DEVICES LIST ADDRESS | | NUMBERS. | | | | 4) THE BATTERY CALCULATION SHOWS A QUANTITY OF 40 | | DEVICES FOR THE HORN/STROBE DEVICES, PLEASE VERIFY | | QUANTITY OF HORN/STROBE DEVICES. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|