Plan Review Notes
Plan Review Notes For Permit 10030547
Permit Number 10030547
Review Stop B
Sequence Number 1
Notes
Date Text
2010-03-22 14:23:08RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- NEED TO PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS TO MEET THE DESIGN PRESSURES OF SEC. R301
 OF 2007 FLORIDA RESIDENTIAL CODE. SEE LIMITATION 5.6 OF
 FLORIDA PRODUCT APPROVAL FL1654-R5 SUBMITTED.
  
 2- DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS
 TO HAVE INTO CONSIDERATION THAT THIS BUILDING IS
 LOCATED ON EXPOSURE "C". SEC. R301.2.1.4.3 OF 2009
 REVISIONS TO THE 2007 FLORIDA RESIDENTIAL CODE.
  
 3- OWES $51.67 FOR UPDATED VALUATION.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712