2010-03-31 08:44:05 | BUILDING PLAN REVIEW |
| PERMIT: 10030541 |
| ADD: 4611 @ GARDEN AVE. |
| CONT: C. R. DUNN |
| TEL: (561)585-2155 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| BUILDING APPROVED WITH EXCEPTION! |
| THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| ASSESSMENT OF RE-INSPECTION FEE(S). |
| |
| 1) SHEET E-20 LIGHT POLE NOTES: CONTRACTOR TO SUBMIT |
| POLE WIND LOADING CALCULATIONS FOR THE POLE AND |
| EMBEDMENT SIGNED AND SEALED BY A FLORIDA REGISTERED |
| STRUCTURAL ENGINEER ILLUSTRATING THAT THE PROPOSED |
| INSTALLATION SHALL MEET THE GIVEN LOADING REQUIREMENTS. |
| |
| 2) ENGINEER OF RECORD HASN'T DECLARED WHAT THE EXPOSURE |
| IS FOR THIS LOCATION, WILL GREATLY EFFECT THE WIND LOAD |
| CALCULATIONS. 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE |
| BUILDING: |
| 2.1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| (KM/HR). |
| |
| 2.2. WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. |
| |
| 2.3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| DIRECTION SHALL BE INDICATED. |
| |
| JIM WITMER C. B. O. |
| COMMERCIAL COMBINATION PLAN REVIEW |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| |