2011-01-05 10:48:52 | ****PROVISOS**** |
| ****ISSUED AT CONTRACTOR'S RISK**** |
| ****REVISION REQUIRED**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2007 |
| FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| |
| |
| 1. ACCESSIBLE ENTRANCE DOOR TO COMPLY WITH MANEUVERING |
| CLEARANCE, FBC 11 FIGURE 25, PULL SIDE. |
| |
| 2. REVISE PLAN TO PROVIDE A RAMP DETAIL WHICH COMPLIES |
| WITH ALL REQUIREMENTS OF FBC 11 4.8. REVISION IS |
| REQUIRED PRIOR TO FIRST INSPECTION. FOR EXAMPLE, DETAIL |
| SHOWN DOES NOT SHOW COMPLIANCE (OR DETAIL IS NON |
| COMPLIANT) WITH REQUIREMENTS SUCH AS EDGE PROTECTION, |
| RAMP LANDING AT BOTTOM, DOOR MANEUVERING CLEARANCE, |
| RAMP RISE. |
| |
| 3. CLARIFY BUILDING TYPE ON PLAN, II B STATED; NON |
| COMBUSTIBLE, SEE FBC CHAPTER 6. |
| |
| 4. PORCH ENCLOSURE STRUCTURAL DETAIL (PREPARED BY |
| STEVEN WALSH, PE) TO BE REVIEWED BY ENGINEER OF RECORD |
| (BERT BEJARANO, PE). |
| |
| 5. ACCESSIBLE BATH SHOWN ON FLOOR PLAN CONFLICTS WITH |
| THE DETAIL MARKED "ACCESSIBLE RESTROOM REQUIREMENTS." |
| SCOPE OF WORK COVERED UNDER THIS PERMIT IS NOT CLEAR. |
| REVISE PLAN TO SHOW WORK TO BE INCLUDED IN THIS PERMIT |
| AND REVISE DETAILS AS NECESSARY.6. |
| |
| 6. SUBMIT DOOR PRODUCT APPROVAL. THIS SHOULD BE |
| REVIEWED BY ENGINEER OF RECORD PRIOR TO SUBMITTAL. |
| ENGINEER TO SPECIFY DESIGN PRESSURES. |
| |
| |
| |
| |
| |