2010-08-02 15:20:38*******PROVISO*******
  
 PLUMBING PERMIT REQUIRED.
 PLUMBING RISER DIAGRAM REQUIRED
  
 1. WITH A CHANGE OF OCCUPANCY TO BUSINESS A DRINKING
 FOUNTAIN WILL BE REQUIRED.
 403.1 MINIMUM NUMBER OF FIXTURES. PLUMBING FIXTURES
 SHALL BE PROVIDED FOR THE TYPE OF OCCUPANCY AND IN THE
 MINIMUM NUMBER SHOWN IN TABLE 403.1.
  
 2. A RISER DIAGRAM WILL BE REQUIRED FOR THE DRINKING
 FOUNTAIN PIPEING
 FBC BUILDING 2007 106.3.5 MINIMUM PLAN REVIEW CRITERIA
 FOR BUILDINGS.