2010-07-29 15:29:14 | *****REVIEW COMMENTS - FIRE ***** |
| |
| 1) ADD FLORIDA FIRE PREVENTION CODE 2007 EDITION (NFPA |
| 1 & NFPA 101) TO THE CODE LIST. |
| |
| 2) PROVIDE BUILDING ADDRESS HAVING NUMBERS CONTRASTING |
| WITH THEIR BACKGROUND. NUMERALS SHALL BE NOT LESS THAN |
| SIX-INCHES IN HEIGHT AND VISISBLE FROM THE ROAD (NFPA |
| 1, SECTION 10.12.1). |
| |
| 3) RAMPS SHALL HAVE HANDRAILS (NFPA 101, SECTION |
| 7.2.2.4.1). PROVIDE RAMP DETAILS. |
| |
| 4) OUTSIDE RAMPS AND LANDINGS SHALL BE DESIGNED TO |
| MINIMIZE WATER ACCUMULATION ON THEIR SURFACES (NFPA |
| 101, SECTION 7.2.5.6.2). |
| |
| 5) PROVIDE TACTILE SIGNAGE AT EXITS (NFPA 101, SECTION |
| 7.10.1.3). |
| |
| 6) PROVIDE EXIT SIGNS WITH DIRECTIONAL CHEVRONS AND |
| ORIENT SIGNS SO THEY ARE VISIBLE (NFPA 101, SECTIONS |
| 7.10.1.8 AND 7.10.2). |
| |
| 7) THE PORCH IS BEING SHOWN AS AN EXIT. IS THE PORCH |
| ENCLOSED? |
| |
| 8) PROVIDE INFORMATION AS TO WHERE THE EXITS DISCHARGE |
| TO THE EXTERIOR OF THE BUILDING. |
| |
| 9) PROVIDE INFORMATION AS TO THE TYPES OF |
| LOCKING/LATCHING MECHANISMS BEING USED ON THE EXIT |
| DOORS. |
| |
| 10) PROVIDE PORTABLE FIRE EXTINGUISHERS PER NFPA 10. |
| |
| 11) PROVIDE INFORMATION ON SMOKE DETECTORS SHOWN ON |
| PLAN. ARE THE DEVICES SMOKE ALARMS OR SMOKE DETECTORS? |
| ARE THEY BATTERY OPERATED OR POWERED BY THE BUILDING? |
| |
| 12) PROVIDE FURNITURE/EQUIPMENT LAYOUT FOR FILE ROOM, |
| RECEPTION, ENTRY FOYER AND CONFERENCE ROOM. |
| |
| 13) DOORS SWINGS BETWEEN TWO OFFICES AND "ACCESSIBLE |
| BATH" BLOCKS EXIT ACCESS PATH. |
| |
| MIKE CARSILLO, BATTALION CHIEF |
| & WESLEY JOLIN |
| FIRE PLAN REVIEW |