2010-04-05 14:22:57 | 2007 FBC W/2009 REVISIONS | | MODEL 'F' - MASTER | | DENIED BY MECHANICAL | | | | 1) SHOW COMPLIANCE WITH FBC R M1602.4 FOR BALANCED | | RETURN AIR. SHOW LOCATIONS AND SIZES OF TRANSFER DUCTS | | OR GRILLS IN THE BEDROOMS. | | | | 2) SUBMIT SPECIFICATIONS FROM THE MECHANICAL EQUIPMENT | | MANUFACTURER SHOWING THAT THE EQUIPMENT, APPLIANCES AND | | SUPPORTS ARE DESIGNED TO RESIST THE WIND PRESSURES | | GENERATED BY A 140 MPH WIND SPEEDS REQUIRED BY FBC R | | M1307.3. | | | | 3) THE MECHANICAL SYSTEM SIZING SUMMARY DOES NOT MATCH | | THE SIZE OF THE UNITS SPECIFIED IN THE EQUIPMENT | | SCHEDULE ON THE MECHANICAL PLANS. | | | | 4) NOTE: THE EQUIPMENT SIZING SUMMARY USES WORST CASE | | ORIENTATION OF THE STRUCTURE. WHEN SUBMITTING FOR | | INDIVIDUAL PERMITS THE ACTUAL ORIENTATION OF THE | | STRUCTURE WILL BE REQUIRED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|