2010-04-05 14:22:572007 FBC W/2009 REVISIONS
 MODEL 'F' - MASTER
 DENIED BY MECHANICAL
  
 1) SHOW COMPLIANCE WITH FBC R M1602.4 FOR BALANCED
 RETURN AIR. SHOW LOCATIONS AND SIZES OF TRANSFER DUCTS
 OR GRILLS IN THE BEDROOMS.
  
 2) SUBMIT SPECIFICATIONS FROM THE MECHANICAL EQUIPMENT
 MANUFACTURER SHOWING THAT THE EQUIPMENT, APPLIANCES AND
 SUPPORTS ARE DESIGNED TO RESIST THE WIND PRESSURES
 GENERATED BY A 140 MPH WIND SPEEDS REQUIRED BY FBC R
 M1307.3.
  
 3) THE MECHANICAL SYSTEM SIZING SUMMARY DOES NOT MATCH
 THE SIZE OF THE UNITS SPECIFIED IN THE EQUIPMENT
 SCHEDULE ON THE MECHANICAL PLANS.
  
 4) NOTE: THE EQUIPMENT SIZING SUMMARY USES WORST CASE
 ORIENTATION OF THE STRUCTURE. WHEN SUBMITTING FOR
 INDIVIDUAL PERMITS THE ACTUAL ORIENTATION OF THE
 STRUCTURE WILL BE REQUIRED.
  