Plan Review Notes
Plan Review Notes For Permit 10030465
Permit Number 10030465
Review Stop B
Sequence Number 4
Notes
Date Text
2010-07-30 12:49:28TRUSS DRAWING REVIEW FOR MODEL "E" WITH GABLE AND HIP
 ROOF OPTIONS
  
 DENIED BY BUILDING
  
 1) THE TRUSS LAYOUTS FROM THE TRUSS ENGINEER ARE NOT
 SIGNED AND SEALED AS REQUIRED BY FS 471.
  
 2) THE DETAILS ON SHEET S-3 OF THE PLANS CALL FOR
 STEP-DOWN TRUSSES AT THE GABLE ENDS FOR THE 2 X 6
 OUTLOOKERS. THE TRUSS DRAWINGS AND LAYOUT DO NOT
 REFLECT THIS. PLEASE CORRECT.
  
 3) THE TRUSS REVIEW LETTERS THAT WERE SUBMITTED BY THE
 ENGINEER OF RECORD ARE NOT SIGNED AND SEALED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]