Plan Review Notes
Plan Review Notes For Permit 10030453
Permit Number 10030453
Review Stop Z
Sequence Number 1
Notes
Date Text
2010-03-23 16:29:36FAILED
  
 1) PROVIDE A CURRENT SURVEY AND SITE PLAN SHOWING THE
 PROPOSED LIGHT POLE LOCATIONS. PLEASE NOTE THAT THE
 LIGHT POLES SHLL BE LOCATED A MINIMUM OF FIVE (5) FEET
 FROM THE PROPERTY LINES.
  
 2) IF THE LIGHT POLES ARE PROPOSED TO BE LOCATED AT THE
 EXTERIOR OF THE PARKING LOT, THEN PLEASE PROVIDE
 PHOTOMETRIC CALCULATIONS AT THE ADJACENT PROPERTY LINE.
  
 3) IF THE LIGHT POLES ARE PROPOSED TO BE LOCATED IN OR
 ADJACENT TO LANDSCAPE AREAS, THEN PROVIDE A LANDSCAPE
 PLAN SHOWING THE LOCATIONS OF THE LIGHT POLES IN
 RELATIONSHIP TO EXISTING TREES. THE LIGHT POSTS SHALL
 NOT CONFLICT WITH TREES. NOTE: IT APPEARS FROM THE
 AERIAL OF THE SITE THAT A NUMBER OF TERMINAL AND
 INTERIOR LANDSCAPE ISLANDS ARE MISSING TREES. THESE
 TREES SHALL BE REPLACED AND THE LIGHT POLES MAY NOT
 CONFLICT WITH THEM.
  
 4) THE ADDITION OF THE LIGHT POLE BASES MAY NOT REDUCE
 THE LANDSCAPE BELOW 15%. THIS CALCULATION SHALL BE
 SHOWN ON THE LANDSCAPE PLAN.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  