2010-04-08 11:09:51 | NOTE: THE DRY VENT BETWEEN WATER CLOSETS IN ROOMS | | 2-204 & 2-203 IS REQUIRED. SEE HIGHLIGHTED AREA ON | | P-201 | | 911.2 VENT CONNECTION. | | THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN | | THE TWO MOST UPSTREAM FIXTURE DRAINS. THE VENT SHALL | | CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE INSTALLED | | IN ACCORDANCE WITH SECTION 905. THE CIRCUIT VENT PIPE | | SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL OR WASTE. | | |
|