Plan Review Notes
Plan Review Notes For Permit 10030438
Permit Number 10030438
Review Stop P
Sequence Number 1
Notes
Date Text
2010-04-08 11:09:51NOTE: THE DRY VENT BETWEEN WATER CLOSETS IN ROOMS
 2-204 & 2-203 IS REQUIRED. SEE HIGHLIGHTED AREA ON
 P-201
 911.2 VENT CONNECTION.
 THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN
 THE TWO MOST UPSTREAM FIXTURE DRAINS. THE VENT SHALL
 CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE INSTALLED
 IN ACCORDANCE WITH SECTION 905. THE CIRCUIT VENT PIPE
 SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL OR WASTE.
  