Plan Review Notes For Permit 10030438 |
Permit Number |
10030438 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-04-07 16:09:53 | REVIEW #: 1ST | | ACTION: DENIED | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. P001 SHOWS CONDENSATE TO DRYWELL OR STORM DRAIN, | | P101 AND PLAN NOTE 1 ON M02 SHOW CONDENSATE TO HUB | | DRAIN. CONDENSATE CANNOT DISCHARGE TO SANITARY SEWER | | PER MUNICIPAL CODE, FBC M 307.2.1. | | | | 2. LOCATION OF FIRE RATED WALLS NOT CLEAR. PROVIDE | | LOCATION OF ALL FIRE RATED WALLS FBC M 607.8. | | | | 3. GENERAL NOTE 13 ON M01 CALLS FOR AN INSTALLATION | | DETAIL FOR EXTERIOR EQUIPMENT TO BE PREPARED BY | | STRUCTURAL SPECIALTY ENGINEER, FBC M301.12. DETAIL WAS | | NOT PROVIDED ON STRUCTURAL SHEETS. | | | | 4. QUANTITIES ON AIR BALANCE SCHEDULES DO NOT MATCH THE | | QUANTITIES ON THE FLOOR PLAN. SHOW QUANTITIES IN | | COMPLIANCE WITH FBC M403.4. | | | | 5. SOME OUTDOOR AIR QUANTITIES SHOWN ON THE SCHEDULE DO | | NOT APPEAR TO MEET THE REQUIREMENTS OF ASHRAE62, FBC | | M403.4. FOR EXAMPLE, AHU5 STATES THAT 260CFM OF OUTSIDE | | AIR IS PROVIDED. SEE TABLE 6-1, EDUCATIONAL FACILITIES | | MEDIA CENTER, 429 CFM REQUIRED. | | | | 6. PRODUCT APPROVAL APPROVED BY DESIGNER OF RECORD | | REQUIRED FOR LOUVERS, FAC RULE 9B-72. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|