2010-04-07 16:09:53REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. P001 SHOWS CONDENSATE TO DRYWELL OR STORM DRAIN,
 P101 AND PLAN NOTE 1 ON M02 SHOW CONDENSATE TO HUB
 DRAIN. CONDENSATE CANNOT DISCHARGE TO SANITARY SEWER
 PER MUNICIPAL CODE, FBC M 307.2.1.
  
 2. LOCATION OF FIRE RATED WALLS NOT CLEAR. PROVIDE
 LOCATION OF ALL FIRE RATED WALLS FBC M 607.8.
  
 3. GENERAL NOTE 13 ON M01 CALLS FOR AN INSTALLATION
 DETAIL FOR EXTERIOR EQUIPMENT TO BE PREPARED BY
 STRUCTURAL SPECIALTY ENGINEER, FBC M301.12. DETAIL WAS
 NOT PROVIDED ON STRUCTURAL SHEETS.
  
 4. QUANTITIES ON AIR BALANCE SCHEDULES DO NOT MATCH THE
 QUANTITIES ON THE FLOOR PLAN. SHOW QUANTITIES IN
 COMPLIANCE WITH FBC M403.4.
  
 5. SOME OUTDOOR AIR QUANTITIES SHOWN ON THE SCHEDULE DO
 NOT APPEAR TO MEET THE REQUIREMENTS OF ASHRAE62, FBC
 M403.4. FOR EXAMPLE, AHU5 STATES THAT 260CFM OF OUTSIDE
 AIR IS PROVIDED. SEE TABLE 6-1, EDUCATIONAL FACILITIES
 MEDIA CENTER, 429 CFM REQUIRED.
  
 6. PRODUCT APPROVAL APPROVED BY DESIGNER OF RECORD
 REQUIRED FOR LOUVERS, FAC RULE 9B-72.
  