Plan Review Notes For Permit 10030437 |
Permit Number |
10030437 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2010-06-29 14:53:26 | 2007 FBC W/2009 REVISIONS | | MODEL 'C' - MASTER | | | | | | 1) THE NEGATIVE PRESSURE SPECIFIED ON THE STRUCTURAL | | PLANS FOR THE SECTION GARAGE DOOR OF -63.4 PSF EXCEEDS | | THE NEGATIVE DESIGN PRESSURE OF -60 PSF LISTED ON THE | | PRODUCT APPROVAL THAT WAS SUBMITTED. PLEASE CORRECT. | | | | 2) SUBMIT TWO SETS OF SIGNED AND SEALED TRUSS DRAWINGS | | COMPLYING WITH R802.1.6.1 THAT HAVE BEEN REVIEWED AND | | APPROVED BY THE STRUCTURAL DESIGNER OF RECORD FOR EACH | | OF THE ROOF OPTIONS. | | | | NOTE: THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE | | EXTERIOR DOORS IS FOR A 6'-8" MAXIMUM DOOR HEIGHT AND | | IS FOR A FIBERGLASS DOOR. THE DOOR SCHEDULE ON THE | | PLANS SPECIFIES THE DOOR HEIGHTS AS 7'-0" AND LISTS | | HOLLOW METAL AND ALUMINUM EXTERIOR DOORS. PLEASE | | CLARIFY. | | | | NOTE: BECAUSE THESE PLANS ARE TO BE MASTERS, THE | | PRODUCT APPROVALS AND TRUSS DRAWINGS ARE REQUIRED TO BE | | SUBMITTED FOR REVIEW BEFORE THE MASTERED PLANS ARE | | APPROVED. THEY WILL BE FILED WITH THE MASTER AND WILL | | NOT BE REQUIRED TO BE SUBMITTED WITH THE PERMITS | | APPLIED FOR UNDER THE MASTER. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|