2010-03-31 13:14:252007 FBC W/2009 REVISIONS
 COLEMAN PARK MASTER MODEL 'C'
  
 DENIED BY MECHANICAL
  
 1) THE LOCATION OF AHU-1 IS SHOWN IN THE STORAGE AREA
 OF THE GARAGE ON A-1.1 AND AT THE BACK OF THE GARAGE ON
 M-1. PLEASE CLARIFY.
  
 2) SUBMIT SPECIFICATIONS FROM THE MECHANICAL EQUIPMENT
 MANUFACTURER SHOWING THAT THE EQUIPMENT, APPLIANCES AND
 SUPPORTS ARE DESIGNED TO RESIST THE WIND PRESSURES
 GENERATED BY 140 MPH WIND SPEED AS REQUIRED BY FBC R
 M1307.3.
  
 3) THE EQUIPMENT SIZING SUMMARY DOES NOT MATCH THE SIZE
 OF THE EQUIPMENT SPECIFIED ON THE PLANS.
  