Plan Review Notes For Permit 10030437 |
Permit Number |
10030437 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-03-31 13:14:25 | 2007 FBC W/2009 REVISIONS | | COLEMAN PARK MASTER MODEL 'C' | | | | DENIED BY MECHANICAL | | | | 1) THE LOCATION OF AHU-1 IS SHOWN IN THE STORAGE AREA | | OF THE GARAGE ON A-1.1 AND AT THE BACK OF THE GARAGE ON | | M-1. PLEASE CLARIFY. | | | | 2) SUBMIT SPECIFICATIONS FROM THE MECHANICAL EQUIPMENT | | MANUFACTURER SHOWING THAT THE EQUIPMENT, APPLIANCES AND | | SUPPORTS ARE DESIGNED TO RESIST THE WIND PRESSURES | | GENERATED BY 140 MPH WIND SPEED AS REQUIRED BY FBC R | | M1307.3. | | | | 3) THE EQUIPMENT SIZING SUMMARY DOES NOT MATCH THE SIZE | | OF THE EQUIPMENT SPECIFIED ON THE PLANS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|