Plan Review Notes For Permit 10030428 |
Permit Number |
10030428 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2010-07-27 15:50:08 | TRUSS DRAWING REVIEW FOR MODEL "A" WITH GABLE AND HIP | | ROOF OPTIONS | | | | DENIED BY BUILDING | | | | 1) THE TRUSS LAYOUTS FROM THE TRUSS ENGINEER ARE NOT | | SIGNED AND SEALED AS REQUIRED BY FS 471. | | | | 2) THE DETAILS ON SHEET S-3 OF THE PLANS CALL FOR | | STEP-DOWN TRUSSES AT THE GABLE ENDS FOR THE 2 X 6 | | OUTLOOKERS. THE TRUSS DRAWINGS AND LAYOUT DO NOT | | REFLECT THIS. PLEASE CORRECT. | | | | 3) THE TRUSS LAYOUT FOR THE HIP ROOF OPTION DIFFERS | | FROM THE ROOF DESIGN ON SHEET S-1 OF THE PLANS AS NOTED | | BY THE ENGINEER AND ARCHITECT OF RECORD FOR THE | | STRUCTURE. PLEASE MAKE CORRECTIONS AS REQUESTED IN | | THEIR REVIEW COMMENTS. | | | | 4) THE TRUSS REVIEW LETTERS THAT WERE SUBMITTED BY THE | | ENGINEER OF RECORD ARE NOT SIGNED AND SEALED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|