2010-03-29 11:10:32 | 2007 FBC W/2009 REVISIONS |
| MODEL 'A' -MASTER |
| |
| DENIED BY BUILDING |
| |
| 1) PERMIT, RADON AND COUNTY IMPACT FEES WILL BE |
| REQUIRED WHEN APPLYING FOR PERMIT. |
| |
| 2) A CONTRACTOR THAT HAS BEEN REGISTERED WITH THE |
| CONSTRUCTION SERVICES DEPARTMENT WILL BE REQUIRED |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. THE STATUS AT |
| THIS TIME IS TBD. |
| |
| 3) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| BE REQUIRED BY THE TIME OF THE FIRST INSPECTION. |
| |
| 4) TWO COPIES OF A SURVEY SHOWING THE PROPOSED LOCATION |
| OF THE STRUCTURE AND THE DISTANCE TO PROPERTY LINES IS |
| REQUIRED. |
| |
| 5) THE FAIR HOUSING DESIGN GUIDE LINES DO NOT APPLY TO |
| SINGLE FAMILY DWELLINGS. ACCORDING TO THE FAIR HOUSING |
| DESIGN MANUAL, THE FAIR HOUSING DESIGN AND CONSTRUCTION |
| REQUIREMENTS OF THE FAIR HOUSING ACT APPLY TO NEW |
| MULTIFAMILY HOUSING CONSISTING OF FOUR OR MORE DWELLING |
| UNITS. |
| |
| 6) TWO COPIES OF CURRENT PRODUCT APPROVALS ARE REQUIRED |
| FOR THE EXTERIOR DOORS, WINDOWS, WINDOW MULLIONS, |
| OVER-HEAD GARAGE DOOR, ROOF SHINGLES, BLOCK LINTELS, |
| ETC. PER DCA RULE 9B-72. |
| |
| 7) FBC R301.2.1.2 REQUIRES ALL GLAZED OPENINGS TO BE |
| PROTECTED FROM WIND-BORNE DEBRIS. IF THE LARGE MISSILE |
| IMPACT RATED WINDOWS INDICATED ON THE PLANS, ARE NOT |
| INSTALLED, THEN STORM PANELS WILL BE REQUIRED. TWO |
| COPIES OF THE PRODUCT APPROVALS FOR THE STORM PANELS, |
| INSTALLATION SCHEDULES AND KEY PLANS WILL BE REQUIRED. |
| |
| 8) THE DOOR FROM THE GARAGE TO THE LIVING AREA IS |
| REQUIRED TO COMPLY WITH FBC R 309 (GARAGE SEPARATION) |
| AND FBC N1103.AB (ENERGY) AND CAN NOT BE A HOLLOW METAL |
| DOOR. |
| |
| 9) THE WINDOW SCHEDULE ON SHEET A1.1 DOES NOT SPECIFY |
| THE TYPE OF WINDOW, SUCH AS SINGLE HUNG, DOUBLE HUNG, |
| CASEMENT, ETC. PLEASE CORRECT. |
| |
| 10) THE DOOR SCHEDULE ON A1.1 LISTS A WOOD OVER-HEAD |
| GARAGE DOOR AND THE NOTES AT THE TOP SPECIFIES A STEEL |
| ONE. PLEASE CORRECT. |
| |
| 11) THE ENERGY CALCULATIONS SPECIFY R-7 INSULATION AT |
| THE EXTERIOR BLOCK WALLS. SHEET A4.1 SPECIFIES R-3 |
| RIGID INSULATION AT EXTERIOR BLOCK WALLS. SECTION |
| N1100.A.1.1 OF THE 2007 FBC ENERGY GLITCH AMENDMENTS |
| ONLY ALLOWS THE R-VALUE OF ADDED INSULATION FOR THE |
| CALCULATIONS. PLEASE CORRECT. |
| |
| 12) SPECIFY THE ATTIC ACCESS SIZE AND LOCATION ON THE |
| PLANS AS REQUIRED BY R807.1. |
| |
| 13) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| SPECIFICATIONS AND INSTALLATION REQUIREMENTS FOR THE |
| SPRAY FOAM INSULATION TO SHOW COMPLIANCE WITH R806.4 |
| AND R314. |
| |
| 14) SUBMIT TWO SETS OF SIGNED AND SEALED TRUSS DRAWINGS |
| COMPLYING WITH R802.1.6.1 THAT HAVE BEEN REVIEWED AND |
| APPROVED BY THE STRUCTURAL DESIGNER OF RECORD OF THE |
| STRUCTURE FOR THE TWO ROOF OPTIONS. |
| |
| 15) ON SHEET A1.1 THE SAFETY GLAZING NOTE SHOULD |
| REFERENCE SECTION FBC R308.4 AND NOT FBC 2406.3. |
| |
| 16) DETAIL 3 ON SHEET A2.1 FAILS TO PROVIDE A |
| CONTINUOUS LOAD PATH FOR THE PENT. ROOF. PLEASE SPECIFY |
| THE RAFTER TO HEADER, HEADER TO KNEE BRACE, BRACE TO |
| POST AND POST TO WALL CONNECTIONS. R 301.1 |
| |
| 17) NOTE 0907 SPECIFIES METAL STUDS AT 18" OC. IS THIS |
| MEANT TO BE 16" OC PLEASE CLARIFY. |
| |
| 18) ON A4.1 NOTE 0903 SPECIFIES 5/8" STUCCO OVER 3/4" |
| PLYWOOD ON THE SOFFIT. TYPICALLY HIGH RIB METAL LATH |
| WITHOUT BACKING IS USED ON THE SOFFIT. HOWEVER, ASTM C |
| 926 REFERENCED BY FBC R703.6.1 REQUIRES THE STUCCO TO |
| BE 7/8" WHEN APPLIED VERTICALLY TO METAL LATH OVER A |
| SOLID BASE. PLEASE CORRECT. |
| |
| 19) SPECIFY THE METHOD AND FASTENERS THAT WILL BE USED |
| TO ATTACH THE FAUX WOOD OUT-LOOKERS. |
| |
| 20) THE TRUSS ANCHOR SCHEDULE ON SHEET S-2 LISTS AN |
| EXPIRATION DATE OF 1/1/2010 FOR ALL CONNECTORS. PLEASE |
| CLARIFY. |
| |
| 21) THE TRUSS ANCHOR SCHEDULE ALSO LISTS PRODUCT |
| APPROVAL NUMBERS THAT ARE EXPIRED. PLEASE CORRECT. ONLY |
| PRODUCTS WITH CURRENT PRODUCT APPROVALS WILL BE |
| ACCEPTED. DCA RULE 9B-72 |
| |
| 22) NOTE: THE BATH EXHAUST RATE IS SPECIFIED AS 100 CFM |
| ON THE PLANS, HOWEVER, FBC R M1507.3 REQUIRES 50 CFM. |
| |