Plan Review Notes For Permit 10030427 |
Permit Number |
10030427 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2010-05-13 10:32:48 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | 1- A) PROVIDE HANDRAILS ON THE MIDDLE OF THE STAIRWAY | | AS REQUIRED BY SEC. R312.1 AND PROVIDE COMPLETE DETAILS | | AND SPECS TO SHOW COMPLIANCE WITH TABLE R301.5. PLANS | | PROVIDED DON'T SHOW ANY. | | B) PROVIDE COMPLETE FRAMING DETAILS AND SPECS FOR | | STAIRS LANDINGS. TABLE R301.5. PLANS DON'T SHOW ANY. | | C) PROVIDE COMPLETE SPECS AND DETAILS FOR LOGGIA | | GUARDRAIL TO SHOW COMPLIANCE WITH TABLE R301.5 | | | | 2- REVISE PLYWOOD SHEATHING NAILING SCHEDULE. ONLY THE | | SPACING FOR ZONE 3 WAS SPECIFIED. MISSING SPACING FOR | | THE OTHER ZONES. | | | | 3- PROVIDE COMPLETE SPECIFICATIONS FOR DECORATIVE | | SHUTTERS SHOWN ON PLANS. SPECIFY TYPE/MATERIAL AND | | FASTENING TO SHOW COMPLIANCE WITH SEC. R301. | | | | 4- PROVIDE PRODUCT APPROVAL (REVIEWED IN WRITING BY THE | | DESIGNER OF RECORD) AS REQUIRED BY DCA RULE 9B-72 FOR | | PRECAST LINTELS SPECIFIED ON PLANS. | | | | 5- REVISE TRUSS PACKAGE TO INCLUDE THE ATTIC LIVE LOAD | | AS REQUIRED BY TABLE R301. TRUSS PACKAGE TO BE HANDLED | | TO THE INSPECTOR AT TIME OF FRAMING INSPECTION. |
|