 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ALL COMMENTS RELATE TO SHEET E-1, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2008 NEC UNLESS
 OTHERWISE NOTED.
  
 1} PROVIDE ELECTRICAL LOAD CALCULATIONS PER ARTICLE
 220, 2008 NEC.
  
 2} INDICATE ROOM DESIGNATIONS ON THE ELECTRICAL PLAN.
 106.1.3 FBC AS AMENDED.
  
 3} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED.
  
 4} INDICATE THE SIZE OF THE EQUIPMENT GROUNDING
 CONDUCTOR FOR THE FEEDER. 215.5.
  
 5} 250.94 BONDING FOR OTHER SYSTEMS.
 AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING
 INTERSYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED
 FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO
 ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE
 DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR
 STRUCTURES. INDICATE ON THE RISER DIAGRAM.
  
 6} 406.11 TAMPER-RESISTANT RECEPTACLES IN DWELLING
 UNITS.
 IN ALL AREAS SPECIFIED IN 210.52, ALL 125-VOLT, 15- AND
 20-AMPERE RECEPTACLES SHALL BE LISTED TAMPER-RESISTANT
 RECEPTACLES. ADD TO NOTES.
  
 7} CIRCUIT #20 BATH/LAUNDRY GFI IS IN VIOLATION OF
 210.11 (C)(2) LAUNDRY BRANCH CIRCUITS. THIS CIRCUIT
 SHALL HAVE NO OTHER OUTLETS.
  
 8} PER 408.4 CIRCUIT DIRECTORY OR CIRCUIT
 IDENTIFICATION, CLARIFY CIRCUITS 29 & 31. ALSO CIRCUIT
 #25 MARKED DINING ROOM, SEE 210.52 (B)(1) FOR SMALL
 APPLIANCE 20 AMP CIRCUIT REQUIREMENT, CLARIFY.
  
 9} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND
 210.52(A)(2). 2008 NEC. SEE REVIEWED PLAN FOR
 DEFICIENCIES IN ALL BEDROOMS, DINING ROOM AND GREAT
 ROOM.
  
 10} INDICATE A DISCONNECTING MEANS FOR THE WATER
 HEATER. SEE 422.16 NEC FOR CORD AND PLUG RESTRICTIONS,
 AND 422.31(B) FOR HARDWIRE REQUIREMENTS.
  