| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 |
| REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| ALL COMMENTS RELATE TO SHEET E-1, UNLESS OTHERWISE |
| NOTED. ALL CODE ARTICLES REFERENCED ARE 2008 NEC UNLESS |
| OTHERWISE NOTED. |
| |
| 1} PROVIDE ELECTRICAL LOAD CALCULATIONS PER ARTICLE |
| 220, 2008 NEC. |
| |
| 2} INDICATE ROOM DESIGNATIONS ON THE ELECTRICAL PLAN. |
| 106.1.3 FBC AS AMENDED. |
| |
| 3} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN |
| THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE |
| INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS |
| DESIGNED. |
| |
| 4} INDICATE THE SIZE OF THE EQUIPMENT GROUNDING |
| CONDUCTOR FOR THE FEEDER. 215.5. |
| |
| 5} 250.94 BONDING FOR OTHER SYSTEMS. |
| AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING |
| INTERSYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED |
| FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO |
| ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE |
| DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR |
| STRUCTURES. INDICATE ON THE RISER DIAGRAM. |
| |
| 6} 406.11 TAMPER-RESISTANT RECEPTACLES IN DWELLING |
| UNITS. |
| IN ALL AREAS SPECIFIED IN 210.52, ALL 125-VOLT, 15- AND |
| 20-AMPERE RECEPTACLES SHALL BE LISTED TAMPER-RESISTANT |
| RECEPTACLES. ADD TO NOTES. |
| |
| 7} CIRCUIT #20 BATH/LAUNDRY GFI IS IN VIOLATION OF |
| 210.11 (C)(2) LAUNDRY BRANCH CIRCUITS. THIS CIRCUIT |
| SHALL HAVE NO OTHER OUTLETS. |
| |
| 8} PER 408.4 CIRCUIT DIRECTORY OR CIRCUIT |
| IDENTIFICATION, CLARIFY CIRCUITS 29 & 31. ALSO CIRCUIT |
| #25 MARKED DINING ROOM, SEE 210.52 (B)(1) FOR SMALL |
| APPLIANCE 20 AMP CIRCUIT REQUIREMENT, CLARIFY. |
| |
| 9} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND |
| 210.52(A)(2). 2008 NEC. SEE REVIEWED PLAN FOR |
| DEFICIENCIES IN ALL BEDROOMS, DINING ROOM AND GREAT |
| ROOM. |
| |
| 10} INDICATE A DISCONNECTING MEANS FOR THE WATER |
| HEATER. SEE 422.16 NEC FOR CORD AND PLUG RESTRICTIONS, |
| AND 422.31(B) FOR HARDWIRE REQUIREMENTS. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |
| |