Plan Review Notes For Permit 10030408 |
Permit Number |
10030408 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2010-03-25 16:53:02 | REVISIONS REQUIRED | | | | 1) THE PRODUCT APPROVAL FOR THE BILCO ROOF HATCH HAS | | MAXIMUM DESIGN PRESSURES OF + OR - 70 PSF. THE ROOF | | PLANS SHOWS THE NEW LOCATION OF THE HATCH IN CORNER | | ROOF ZONE 3. THIS ROOF HATCH WILL NEED TO BE LOCATED IN | | ROOF ZONE 1 WHICH HAS AN UPLIFT PRESSURE OF - 46.7 PSF | | PER DRAWING S-2 OF THE PLANS. PLEASE CORRECT. | | | | 2) STEEL DECK SYSTEM LIMITATION NUMBER 1 ON PAGE 27 OF | | THE PRODUCT APPROVAL REQUIRES FIELD WITHDRAWL | | RESISTANCE TESTING IN COMPLIANCE WITH TAS 105. RAS 117 | | CALCULATIONS ARE BASED ON A FASTENER RESISTANCE OF | | -250.469 LBF. |
|