2010-03-18 08:33:13 | 2007 FBC W/2009 REVISIONS | | COMMERCIAL RE-ROOF | | | | DENIED BY BUILDING | | | | 1) SUBMIT TWO CURRENT COPIES OF PRODUCT APPROVALS FOR | | THE SARNAFIL ROOFING MEMBRANE. THE ONES THAT WERE | | SUBMITTED EXPIRED ON 7/5/2006. THE CURRENT ONE IS NOA | | NO 08-0717.09. | | | | 2) SPECIFY THE APPROVED ASSEMBLY FROM THE NOA THAT WILL | | BE INSTALLED. SPECIFY THE INSULATION, FASTENER DENSITY | | AND MAXIMUM DESIGN DESIGN PRESSURE FOR THE ASSEMBLY. IF | | INCREASED FASTENER DENSITY IS REQUIRED TO RESIST ROOF | | UPLIFT PRESSURES IN ROOF ZONES 2 AND 3, SUBMIT TWO SETS | | OF RAS 117 CALCULATIONS FROM A FLORIDA REGISTERED | | ENGINEER OR ARCHITECT. SEE STEEL DECK SYSTEM AND | | GENERAL LIMITATIONS AT THE END OF THE NOA. | | | | 3) SUBMIT TWO CURRENT COPIES OF PRODUCT APPROVALS FOR | | THE NEW BILCO ROOF HATCH THAT WILL BE INSTALLED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|