2010-03-18 08:33:132007 FBC W/2009 REVISIONS
 COMMERCIAL RE-ROOF
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO CURRENT COPIES OF PRODUCT APPROVALS FOR
 THE SARNAFIL ROOFING MEMBRANE. THE ONES THAT WERE
 SUBMITTED EXPIRED ON 7/5/2006. THE CURRENT ONE IS NOA
 NO 08-0717.09.
  
 2) SPECIFY THE APPROVED ASSEMBLY FROM THE NOA THAT WILL
 BE INSTALLED. SPECIFY THE INSULATION, FASTENER DENSITY
 AND MAXIMUM DESIGN DESIGN PRESSURE FOR THE ASSEMBLY. IF
 INCREASED FASTENER DENSITY IS REQUIRED TO RESIST ROOF
 UPLIFT PRESSURES IN ROOF ZONES 2 AND 3, SUBMIT TWO SETS
 OF RAS 117 CALCULATIONS FROM A FLORIDA REGISTERED
 ENGINEER OR ARCHITECT. SEE STEEL DECK SYSTEM AND
 GENERAL LIMITATIONS AT THE END OF THE NOA.
  
 3) SUBMIT TWO CURRENT COPIES OF PRODUCT APPROVALS FOR
 THE NEW BILCO ROOF HATCH THAT WILL BE INSTALLED.
  