Plan Review Notes
Plan Review Notes For Permit 10030366
Permit Number 10030366
Review Stop M
Sequence Number 1
Notes
Date Text
2010-03-29 10:30:49PASS PROVISO
 1) PLEASE INSTALL RETURN AIR IN ROOM 113 OFF OF RTU # 3
 PER SECTION 601.4 BALANCED RETURN AT 2007 FBC (M)
 2 PLEASE PROVIDE A LETTER FROM THE A/C MANUFACTURE
 STATING THAT NO WAY SHAPE OR FORM CAN RTU # 1 PRODUCE
 MORE THAN 2000 CFM .PLEASE REFER TO SECTION 606.2.21
 SUPPLY AIR .
 PLAN REVIEW BY HAROLD MOSER 561- 805 - 6732