Plan Review Notes For Permit 10030273 |
Permit Number |
10030273 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-03-24 14:53:12 | *****PROVISO***** | | | | THE FIRE ALARM PLAN (FS-1, FS-5, FS-6) WAS FIRE-STAMPED | | ACCORDINGLY; READY FOR PERMIT ISSUANCE. | | | | PLEASE BE ADVISED THAT THE FOLLOWING REVISIONS ARE | | REQIRED PRIOR TO A FIRE ALARM FINAL (CODE #302) | | INSPECTION: | | 1. SHOW THE NECESSARY FIRE ALARM DEVICES IN THE WOMEN'S | | BATH / WOMEN'S LOCKER AREA. AMEND APPROPIATE SHEET(S) | | AS NECESSARY. | | 2. AS PER LOCAL CODE, DUCT SMOKE DETECTORS SHALL | | INITTIATE A GENERAL FIRE ALARM. MAKE NECESSARY | | ADJUSTMENTS TO THE FIRE ALARM MATRIX AND SEQUENCE OF | | OPERATIONS. | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | | | | | | 2. |
|